Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
6-10
Figure 6-2. 45° Electrode Plane
To insure accuracy of resistance readings, zero out multimeter by shorting
and touching the leads together.
Table 6-6. Uninstalled Rosemount 8705 / 8707
Flanged Sensor Tests
Measuring at Connections
Hazardous Location Certifications
N0
N5, KD
18 and Electrode
(1)
(1) It is difficult to tell from visual inspection alone which electrode is wired to which number terminal in
the terminal block. Measure both electrodes. One electrode should result in an open reading, while
the other electrode should be less than 275
.
19 and Electrode
17 and Grounding Electrode
17 and Ground Symbol
17 and 18
Open
Open
17 and 19
Open
Open
17 and 1
Open
Open
Table 6-7. Uninstalled Rosemount 8711 Wafer Sensor Tests
Measuring at Connections
Hazardous Location Certification
N0
N5, E5, CD
18 and Electrode
(1)
(1) Measure the electrode closest to the junction box
19 and Electrode
(2)
(2) Measure the electrode farthest away from the junction box.
17 and Grounding Electrode
17 and Grounding Symbol
17 and 18
Open
Open
17 and 19
Open
Open
17 and 1
Open
Open
275
61k
R
75k
275
61k
R
75k
0.3
0.3
0.3
0.3
0.3
61k
R
75k
275
61k
R
75k
0.3
0.3
0.3
0.3
Содержание 8732 Series
Страница 2: ......
Страница 4: ......
Страница 10: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 TOC 6 ...
Страница 26: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 2 14 ...
Страница 38: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 3 12 ...
Страница 92: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 A 8 ...
Страница 107: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 15 Rosemount 8732 Figure B 1 ATEX Installation 1 of 6 ...
Страница 108: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 16 Figure B 2 ATEX Installation 2 of 6 ...
Страница 109: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 17 Rosemount 8732 Figure B 3 ATEX Installation 3 of 6 ...
Страница 110: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 18 Figure B 4 ATEX Installation 4 of 6 ...
Страница 111: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 19 Rosemount 8732 Figure B 5 ATEX Installation 5 of 6 ...
Страница 112: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 20 Figure B 6 ATEX Installation 6 of 6 ...
Страница 113: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 21 Rosemount 8732 Figure B 7 FM Certified I S Output 1 of 4 ...
Страница 114: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 22 Figure B 8 FM Certified I S Output 2 of 4 ...
Страница 115: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 23 Rosemount 8732 Figure B 9 FM Certified I S Output 3 of 4 ...
Страница 116: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 24 Figure B 10 FM Certified I S Output 4 of 4 ...
Страница 117: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 25 Rosemount 8732 Figure B 11 CSA Certified I S Output 1 of 2 ...
Страница 118: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 26 Figure B 12 CSA Certified I S Output 2 of 2 ...
Страница 119: ...Reference Manual 00809 0100 4663 Rev BA January 2010 B 27 Rosemount 8732 Figure B 13 CSA Installation ...
Страница 120: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 B 28 Figure B 14 Factory Mutual Hazardous Locations ...
Страница 186: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 H 8 ...
Страница 189: ......