Reference Manual
00809-0100-4530, Rev DD
May 2016
5.3.2
Set alarm limits
The alarm limits that are set in the host system need to be adjusted for the expected
maximum product level rate and configured Damping Value.
When setting the high alarm limit, a safety margin (see
) should be subtracted
from the desired high alarm limit. For the low alarm limit, the same safety margin should be
added to the desired low alarm limit.
The safety margin ensures that the response time of the device is taken into account when
specifying the alarm limits. See table
or
(if Signal Quality Metrics is
turned on) to determine the safety margin for your application.
Note
Alert limit values must be outside the Blind Zones and preferable outside areas with
reduced accuracy.
Figure 5-1. Safety Margin for Alarm Limits
Safety margin
High alarm limit
Desired high
alarm limit
Low alarm
limit
Desired low
alarm limit
Safety margin
Lower reference point
Blind Zones
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...