May 2016
Reference Manual
00809-0100-4530, Rev DD
317
C.8.2
Review installation guidelines
The following installation guidelines should be considered when mounting the transmitter:
Only probe type 3V or 4U must be used. Check the “VC” and “R3” marking on the
seal.
The maximum probe length is 13.1 ft (4 m) for probe type 3V and 7.5 ft (2.3 m) for
probe type 4U.
Pipe/Chamber is the only supported mounting type. See below for supported pipe
inner diameters:
Probe End Projection is disabled when Vapor Compensation is enabled.
Trim Near Zone shall not be used when Dynamic Vapor Compensation is used.
Probe type
Chamber size
Supported pipe inner diameter
3V
3 to 4 in.
Minimum 2 in. (50 mm)
4U
2 in.
1.5 to 2.05 in. (38 to 52 mm)
Probe type 4U (rigid single)
for 2 in. chambers
Probe type 3V (coaxial)
for 3-4 in. chambers