About Alarms
Alarms
The 3490 Series Control Unit can detect the following alarm conditions:
•
PV value out-of-limits.
•
Current Output saturated
(Standard:
≤
3.9mA or
≥
20.8mA, NAMUR NE43:
≤
3.8mA or
≥
20.5mA)
•
Logging memory filling (model 3493 only).
•
Logging memory full (model 3493 only).
•
Digital input is configured to force an alarm when active.
•
Maximum number of failed Custom relay operation attempts.
•
Current Input saturated.
•
Rising liquid level.
•
Relay operation count limit exceeded.
•
Relay run time limit exceeded.
•
Low pump efficiency (models 3491 and 3492 only).
•
Relay inactivity.
Parameter D830 shows a list of active alarms. In addition, alarms are
indicated by means of Relays, Current Output, or both (see below).
Table 4-15 on page 4-62 has a summary of reporting methods for alarms.
Alarm indication selection
For each alarm listed in Section “Alarms“ on page 4-60, there is a dedicated
parameter in the ALARM menu for selecting the method of indication for that
alarm.
Menu: MAIN MENU / SETUP / [CONTROL UNIT /] OUTPUT / ALARM
P540
PV Over Limits
(Factory default is "None")
Select the indication method for the alarm condition that occurs if the PV
value is outside pre-set limits.
See also Section “PV limits Relay“ on page 4-53.
P541
mA Out Sat
(Factory default is "None")
Select the indication method for the alarm condition that occurs if the
Current Output is
≤
3.8mA or
≥
20.5mA
P542
Log mem filling
(Factory default is "None")
Select the indication method for the alarm condition that occurs if the
available logging memory is low. See also Section “P593: Low Memory
Alarm“ on page 4-35.
P543
Digital Input
(Factory default is "None")
Select the indication method for the alarm condition that only occurs if a digital
input is configured to force this alarm and that digital input is active - see
Section “Digital Inputs IN1 and IN2“ on page 4-34.
P544
Max retries
(Factory default is "None")
Select the indication method for the alarm condition that only occurs if a
Custom relay operation is unable to complete as specified, even after a
pre-set number of attempts (P257). See also Section “Custom“ on page 4-55.
Содержание 3491
Страница 2: ......
Страница 4: ......
Страница 8: ...Reference Manual 00809 0100 4841 Rev AA May 2007 Rosemount 3490 Series 1 4 ...
Страница 12: ...Reference Manual 00809 0100 4841 Rev AA May 2007 Rosemount 3490 Series 1 4 ...
Страница 32: ...Reference Manual 00809 0100 4841 Rev AA May 2007 Rosemount 3490 Series 3 14 ...
Страница 108: ...Reference Manual 00809 0100 4841 Rev AA May 2007 Rosemount 3490 Series 4 76 ...
Страница 134: ...Reference Manual 00809 0100 4841 Rev AA May 2007 Rosemount 3490 Series B 8 ...
Страница 148: ...Reference Manual 00809 0100 4841 Rev AA May 2007 Rosemount 3490 Series D 4 ...
Страница 151: ......