2-21
Level Controller Overview and Installation
Check for Leaks
Check all process penetrations for leaks. Process leaks can cause death
or serious injury.
Field Wiring
(Power and Signal)
Make field wiring connections (see Figure 2-12). These connections
provide both power and signal wiring.
For
all
installations, wiring connections must be made in accordance
with local or national installation codes such as the NEC NFPA 70.
Make sure only qualified personnel perform these procedures.
NOTES
• Do not run field wiring in conduit or open trays with other power
wiring, or near heavy electrical equipment.
• Field wiring need not be shielded, but use twisted pairs for best
results.
• To ensure communication, wiring should be 24 AWG or larger
and not exceed 5,000 feet (1,500 meters).
• For connections in ambient temperatures above 140 °F (60 °C),
use wiring rated for at least 194 °F (90 °C).
1. Remove the cover on the side marked FIELD TERMINALS on the
electronics housing. Do not remove the instrument cover in
explosive atmospheres when the circuit is alive.
2. Connect the lead that originates at the positive side of the power
supply to the terminal marked “+ PWR.” Be sure to include loop
resistance. Avoid contact with leads and terminals.
3. Connect the lead that originates at the negative side of the power
supply to the terminal marked “– PWR.”
4. Connect the I/P or other actuator device to “+ OUT” and “– OUT.”
NOTE
If you are not connecting the OUT terminals to an actuator device,
you must install a jumper wire between “+ OUT” and “– OUT” for
proper operation.
Compression Fitting
Rubber Bushing
(Slide stop to edge
of armored cable)
Washer
Cap
RTD Cable Adapter
and Connector
(Connects to Model 3095 MV)
3
095
-0
020
D
01
A
¾ to ½–in. NPT Adapter
(Screws into RTD Connection Head)
1100
V
> R
L
> 250
V
+
–
I
P
FIGURE 2-12. Field
Wiring Connections.
+
–
+
–
PWR
OUT
Level
Controller
User-Provided
Power Supply
(see page 2-18)
–
+
Actuator
Device
Содержание 3095
Страница 2: ......
Страница 4: ......
Страница 8: ...viii ...
Страница 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Страница 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Страница 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Страница 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Страница 100: ...Rosemount Model 3095 Multivariable Level Controller C 2 FIGURE 3 1 Explosion Proof Drawing Factory Mutual 3095 1025A01A ...
Страница 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Страница 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Страница 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Страница 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Страница 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Страница 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Страница 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Страница 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Страница 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Страница 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Страница 112: ...Rosemount Model 3095 Multivariable Level Controller C 14 FIGURE 3 4 Index of I S CSA for 3095 3095 1021A01A ...
Страница 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Страница 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...