Quick Installation Guide
00825-0400-4101, Rev AA
March 2011
Rosemount 2051
12
S
TEP
5
CONTINUED
...
Table 1. LOI Button Operation
Figure 8. LOI Menu
Class 2 Master
The Rosemount 2051 PROFIBUS DD and DTM files are available at
www.EmersonProcess.com/Rosemount or by contacting your local salesperson. See
Table 2 for steps to configure the transmitter for Pressure measurement. See product
manual (00809-0300-4101) for Flow or Level configuration instructions.
Table 2. Pressure Configuration via Class 2 Master
Button
Action
Navigation
Character Entry
Save?
Scroll
Moves down menu
categories
Changes character
value
(1)
(1)
(1) Characters blink when they can be changed.
Changes between Save
and Cancel
Enter
Selects menu
category
Enters character and
advances
Saves
Steps
Actions
Set blocks to Out of Service
Put Transducer Block into Out of Service mode
Put Analog Input Block into Out of Service mode
Select Measurement Type
Set Primary Value type to Pressure
Select Units
Set Engineering Units
- Primary and secondary units must match
Enter Scaling
Set Scale In in Transducer Block to 0 - 100
Set Scale Out in Transducer Block to 0 - 100
Set PV Scale in Analog Input Block to 0 - 100
Set Out Scale in Analog Input Block to 0 - 100
Set linearization in Analog Input Block to none
Set blocks to Auto
Put Transducer Block into Auto mode
Put Analog Input Block into Auto mode
1. ADDRESS
6. IDENTIFICATION #
7. EXIT
4. DAMPING
5. DISPLAY
3. UNITS
2. CALIBRATION
PRESSURE
FLOW
LEVEL
TEMPERATURE
0-126
ZERO
LOWER SENSOR
UPPER SENSOR
RESET FACTORY
00825-0400-4101.fm Page 12 Friday, March 25, 2011 1:34 PM