Reference Manual
00809-0100-4792, Rev CA
August 2010
Rosemount 1495, 1496
www.rosemount.com
Section 2
Installation, Location, and
Orientation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Receiving and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2
Installation Configuration . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2
Straight Run Requirements . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
This section describes the orientation, location and alignment limits for
installing the Rosemount 1495 Orifice Plate, 1496 Flange Union. Read it
thoroughly before starting the installation.
SAFETY MESSAGES
Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Please refer to
the following safety messages before performing any operation in this section.
INSTALLATION
CHECKLIST
The following list is a summary of the steps required to complete a
Rosemount 1495 Orifice Plate installation. If this is an entirely new
installation, begin with step 1. If the Flange Union is already in place, verify
that the orifice flange size and rating match the recommended specifications,
and begin with step 5.
1.
Determine where the Rosemount 1495 Orifice Plate, 1496 Flange
Union is to be placed within the piping system.
2.
Establish the proper orientation as determined by the intended
service for the orifice plate.
3.
Review Appendix B Recommended Installation Requirements.
4.
Confirm the Rosemount 1495 and/or 1496 configurations.
5.
Measure the pipe’s internal diameter (ID), preferably at 1 x ID from
the orifice flange (upstream or downstream), or at the tap location for
flange taps.
NOTE
Providing the pipe internal diameter at the time of purchase is necessary to
maintain published orifice plate accuracy.
6.
Install the hardware. Refer to Section 3 for 1495 Orifice Plate
installation and Section 4 for 1496 Orifice Flange Union installation.
7.
Check for leaks.
8.
Commission the orifice plate flowmeter.
Failure to follow these installation guidelines could result in death or serious injury:
* Make sure only qualified personnel perform the installation.
Содержание 1495
Страница 2: ......
Страница 4: ......
Страница 12: ...Reference Manual 00809 0100 4792 Rev CA August 2010 Rosemount 1495 1496 2 4 ...
Страница 52: ...Reference Manual 00809 0100 4792 Rev CA August 2010 Rosemount 1495 1496 A 14 ...
Страница 66: ...Reference Manual 00809 0100 4792 Rev CA August 2010 Rosemount 1495 1496 B 14 ...
Страница 68: ...Reference Manual 00809 0100 4792 Rev CA August 2010 Rosemount 1495 1496 C 2 NOTES ...
Страница 69: ......