Side 30
Mounting Instructions
1.Mounting to the wall
The nursing table is being supplied with a set (8 pcs) of screws and rawlplugs, which
is ONLY used to mount the unit in a concrete wall. The installer must always
examine the material, condition and strength of the wall and use appropriate screws
and rawlplugs.
Nursing table has a max user weight of 75 kg.
Maximum load in the top screws are 26kg for each screw.
The holes for fastening can be marked up on the wall, four possibilities in the top,
and four in the bottom of the frame. Place the frame against the wall and make sure
it is horizontal. The frame is standing on two adjustable feet. The holes in the frame
are all Ø 10 mm. Remove the frame and drill the holes.
Force for each of the four screws in top of the unit
:
F
screw
= (75 kg * 830)/(790 * 4 screws)
F
screw
=26 kg for each screw
If you have other objects mounted right next to this nursing table, you have to
consider the risk of trapping, and therefore consider a safe distance to other
objects.
Make sure that no dust or other obstacles are interfering with the rollers, chain,
sprocket or gas springs. This can cause malfunction and damage the system
F=Screw
Содержание Medi 2
Страница 10: ...Side 10 Montagevejledning 2 Montage af dækkappe ...
Страница 11: ...Side 11 Montagevejledning 3 Montage af bordplade ...
Страница 12: ...Side 12 Montagevejledning 4 Tilslutning af vand og afløb ...
Страница 32: ...Side 32 Mounting instructions 2 Mounting of cover ...
Страница 33: ...Side 33 Mounting instructions 3 Mounting of tabletop ...
Страница 34: ...Side 34 Mounting instructions 4 Connection of water and drain ...
Страница 54: ...Side 54 Montageanleitung 2 Montage der Abdeckung ...
Страница 55: ...Side 55 Montageanleitung 3 Montage der Tischplatte ...
Страница 56: ...Side 56 Montageanleitung 4 Anschluss von Wasser und Ablauf ...
Страница 66: ...Side 66 Reklamationen Bitte siehe Allgemeine Verkaufs und Lieferungsbedingungen auf www ropox com ...
Страница 67: ...Side 67 ...