![Ropex RESISTRON RES-5007 Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/ropex/resistron-res-5007/resistron-res-5007_operating-instructions-manual_1486113031.webp)
Device functions
Version 1
RES-5007
Page 31
Part 2 of 3: Error messages (warnings)
NOTE:
The specified error messages are first output as warnings (actual value output switches between two
values; alarm LED flashes; alarm output is not active). After activation of the START signal, it is output as a
malfunction (actual value output no longer changes, see bold-italic values; alarm LED is permanently lit; alarm
output is active).
Error
no.
Actual
value
output
Voltage
[V]
Cause
Measure if initial start-
up
Measure of machine in
operation, heating ele-
ment not changed
104
5.33
10
Current signal incorrect
Impulse transformer incorrectly
sized
Perform
AUTOCAL,
Check transformer speci-
fication,
Error ranges
Error ranges
(“Loose connection”)
105
Voltage signal incorrect
Impulse transformer incorrectly
sized
106
Voltage and current signal
incorrect
Impulse transformer incorrectly
sized
302
Temperature too low
Calibration not performed
Loose connection
Ambient temperature fluctu-
ates
Perform
AUTOCAL
and/or
Error ranges
(“Loose connection”)
303
Temperature too high
Calibration not performed
Loose connection
Ambient temperature fluctu-
ates
211
6.00
10
Data error
Perform
AUTOCAL
Perform
AUTOCAL