Chapter 3 Accura 2350-TEMP Operation/Setup
Accura 2350-TEMP User Guide
Page 32
ⓒ
2020 Rootech Inc. All Rights Reserved
Buzzer
Screen
Setup item
Range
Default
Function
Disable / Button Enable / Event Enable / Both
Enable
Button
Enable
Pulse Period
0.2
–
5.0 sec
1.0 sec
Pulse On-time
1
0.1
–
5.0 sec
0.5 sec
1. When the Buzzer-On time is shorter than the cycle, the device gives users intermittent beeping sound. However,
when the Buzzer-On time is same as or longer than the cycle, it provides users with continuous sound.
Setup Exit
Screen
Setup item
Range
Default
Timeout
60
–
3600 sec
600 sec
SYSTEM Setup
Screen
Setup item
Range
Default
Module ID
0 - 39
255
1
Temp Unit
Celsius / Fahrenheit
Celsius
Summary Type
Sets up the main screen of the SUMMARY
column
Highest / All TSEN
Highest
1. It indicates the ID number assigned as the factory default value. Communication is unavailable.