RJ12 Communication Port
It is located on the left and right sides of the Accura 2350-TEMP module and is used when connecting
the Accura 2350-TEMP module with the Accura 2350 module in a daisy chain topology. RJ12A and
RJ12B ports have the same functions.
Item
Description
Port name
2 ports (RJ12A, RJ12B)
Connector type
RJ12 connector
Protocol
RS-485 based internal dedicated protocol
RJ45 Communication Port
It is located at the back of the Accura 2350-TEMP module and is used when connecting Accura 2350-
TEMP to Accura TSEN.
Item
Description
Connector type
RJ45 connector
Protocol
RS-485 based internal dedicated protocol
RESET Button
It is used to reset external temperature events on the Accura 2350-TEMP module. Users can also reset
event alarms by enabling the reset function for the DI and the EVENT button on the Accura 2350-TEMP
module.
Digital Input (DI)
The Accura 2350-TEMP module supports 1 uninsulated DI channel. Users can reset settings for event
alarms by connecting a switch to the DI port and controlling the switch in the status the reset function
for the DI is enabled.
Item
Description
Port name
DI, DIG
Connector type
Screw-type terminal
Wire specs
0.21
–
3.5 mm
2
(24
–
12AWG)
Insulation method
Uninsulated
Input type
Open/Closed contact point (internal power is used)
Minimum time the contact
point is in closed status
20 msec