Chapter 3 Accura 2350-TEMP Operation/Setup
Accura 2350-TEMP User Guide
Page 30
ⓒ
2020 Rootech Inc. All Rights Reserved
EVENT RESET
It indicates the setup for resetting event alarms. Users can reset alarms on external temperature events
on the Accura 2350-TEMP module using the RESET button or the Digital Input and the EVENT button.
For events on the Accura TSEN module, users can reset events only with the RESET button on the device.
Users can check detailed data on temperature events with the EVENT button on the front of the Accura
2300S device, but cannot reset event alarms on the device.
Screen
Setup item
Range
Default
DI
- Disable : the reset function is disabled
- Event LED: the function to reset the Event
LED is enabled.
- DO: the function to reset the DO is enabled.
- Both: the function to reset the Event LED and
DO is enabled
Disable
EVENT Btn
1
- Disable : the reset function is disabled
- Event LED: the function to reset the Event
LED is enabled
- DO: the function to reset the DO is enabled.
- Both: the function to reset the Event LED and
DO is enabled
Disable
1. If users activate the selected setup item and long press the EVENT button on the Accura 2350-TEMP module,
alarms on the selected event are reset.
DIO Setup
It indicates the setup for Digital Inputs (DI) and Digital Outputs (DO).
DI
Screen
Setup item
Range
Default
Polarity
Polarity of the logic value for the contact point
of the DI
- Normal mode
0: Open point 1: Closed point
- Reverse mode
0: Closed point 1: Open point
Normal