Page 72
Appendix A Specifications
Voltage Input
Rating
0 to 600V 3 to L-L, 0 to 457V 3 to L-N
Use PTs for voltages over 457V line to line in three phase 3 wire open delta
direct connection mode.
Calibration
60 to 220V(per phase)
Wiring Mode
1P2W, 1P3W, 3P3W, 3P4W
Burden
0.02VA/phase @ 220V
Pickup Voltage
25V per phase
Impedance
3M
Ω
/phase
Wire
2.1 to 3.5 mm
2
(14 to 12 AWG)
Current Input
Rating
5A nominal/10A full scale 3 -
Calibration
0.05 to 10A(per phase)
Burden
Max. 0.005VA/phase @ 10A
Pickup Current
20mA
Wire
2.1 to 6 mm
2
(14 to 10 AWG)
Module
Digital input
channel
Dry contact
Digital output
channel
Dry contact, AC/DC 400V 350mA(1000mA Peak)
Analog input
channel
0 to 20mA, 12bit
Analog output
channel
4 to 20mA, 12bit
Isolation
All inputs/outputs
AC 2,500V for a minute
Environmental Condition
Operating temp
-20 to 70
℃
(-4 to 158
℉
)
Storage temp
-40 to 85
℃
(-40 to 185
℉
)
Humidity
5-95%(non-condensing)
Weight
Meter + basic module
0.5kg
Meter + basic
extension module
0.7kg