Appendix C Test Report
Measuring Test
IEC 62053-22, Electricity Meter Equipment: active energy for Class 0.5S
Current range
Power factor
Class 0.2S/ 0.5S
Accura 3300S
0.05A < I < 0.25A
1.0
± 0.4%/ ± 1.0%
± 0.4%
0.25A < I < 10.0A
1.0
± 0.2%/ ± 0.5%
± 0.2%
0.10A < I < 0.50A
0.5 inductive
± 0.5%/ ± 1.0%
± 0.5%
0.8 capacitive
± 0.5%/ ± 1.0%
± 0.5%
0.50A < I < 10.0A
0.5 inductive
± 0.3%/ ± 0.6%
± 0.5%
0.8 capacitive
± 0.3%/ ± 0.6%
± 0.5%
0.50A < I < 10.0A
0.25 inductive
± 0.5%/ ± 1.0%
± 0.5%
0.5 capacitive
± 0.5%/ ± 1.0%
± 0.5%
Parameter Accuracy
Item
Display range
†
Accura 3300S
Voltage[L-N]
0.0 ~ 9999V, kV
±
0.2% Reading
Voltage[L-L]
0.0 ~ 9999V, kV
±
0.2% Reading
Current
0.000 ~ 9999A, kA
±
0.2% Reading
Power
Active
0.000 ~
±
9999kW, MW
Class 0.5S
‡
Reactive
0.000 ~
±
9999kVar, MVar
±
0.5% Reading
Apparent
1
0.000 ~
9999kVA, MVA
±
0.5% Reading
Energy
2
Active
0 ~
±
999,999,999kWh
Class 0.5S
Reactive
1
0 ~
±
999,999,999kVarh
±
0.5% Reading
Apparent
1
0 ~ 999,999,999kVAh
±
0.5% Reading
Hz
45 ~ 70Hz
0.01Hz Reading
PF
2
-1.000 ~ 1.000
±
0.5% Reading
THD
Voltage
0.0 ~ 999.9%
±
1.0% Full Scale
Current
0.0 ~ 999.9%
±
1.0% Full Scale
Demand
Power
0.000 ~
±
9999kW, MW
Class 0.5S
Current
0.000 ~ 9999A, kA
±
0.2%
†
Refer to the calibration range specified in
“
Appendix A
”
for the information on the measuring range of voltage and
current for guaranteed accuracy.
‡
Class 0.5S means IEC62053-22 Class 0.5S.
1It is available only via RS485 communication. 2 Power and power factor values