Appendix A Specifications
Accura 2350-VDC User Guide
Page 28
ⓒ
2014 Rootech Inc. All Rights Reserved
Appendix A Specifications
Analog Input : 8 DC Voltage Channels
Ch 1
Ch 2
Ch 3
Ch 4
Ch 5
Ch 6
Ch 7
Ch 8
Port name
V
DC1
V
DC2
V
DC3
V
DC4
V
DC5
V
DC6
V
DC7
V
DC8
Ground
1
V
DC1G
V
DC2G
V
DC3G
V
DC4G
V
DC5G
V
DC6G
V
DC7G
V
DC8G
1.DO1G , DO2G
… and DO
8G are different grounds corresponding to each channel.
Item
Description
Connector type
Terminal block
Wire specification
1.5 to 3.5 mm
2
(16 to 12 AWG), copper or aluminum
Input voltage
DC voltage -50 V to 50 V
Isolation/channel
AC 2,000 V for 1 minute, 8 channels
(differential inputs, non-isolated between channels)
Input resistance
Higher than 2 M
Ω
Measurement accuracy
±
0.5% FS
1
Event
“
Over
”
/
”
Under
”
event
2
selectable based on the threshold value for each channel
1. Full Scale (FS) indicates 50 V.
2.
An “
Over
”
event indicates an event where the measured value rises above the threshold. An
“
Under
”
event
indicates an event where the measured value falls below the threshold. Over and Under voltage events consist of
start and end events. Either event can be configured.
Item
Description
Power supply
Receives power from Accura 2300[S] through the RJ12 6C communication line
Current consumption
0.11A @ 5V RJ12 power supply
General
Weight
164 g
Excluding mounting wings
167 g
Including mounting wings
Environmental Conditions
Operating temperature
-20 to 70
℃
(-4 to 158
℉
)
Safe operating temperature
1
-20 to 65
℃
(-4 to 149
℉
)
Storage temperature
-20 to 85
℃
(-40 to 185
℉
)
Operating humidity
5 - 95 % (non-condensing)
Operating altitude
Up to 2,000 m
1. Compliant with the UL61010-1 standard (3rd edition)
Содержание Accura 2350-VDC