Temperature Events 

Temperature  events  include  events  on  internal  temperatures,  external  temperatures,  and  temperature 

differences. Each temperature event consists of a start event and an end event. The start event provides 

data  on  the  temperature  measured  when  an  event  is  detected.  The  end  event  offers  the  highest 

temperature measured during the event interval. 

 

Fig 4.1 Temperature Event Screen 

Start Event on Internal Temperature 

End Event on Internal Temperature 

 

 

 

The temperature event screen indicates the following items. 

 

Item   

 

Description 

First row   

E[d][d][d] 

1

  Displays the event number, Range: 000 - 999 

Second row 

M.tMP 

Displays the module where the event occurred : TEMP module 

Third row 

In.[d]

 1

.S 

Accura TSEN.[d]: the start event on the internal temperature 

In.[d]

 1

.E 

Accura TSEN.[d]: the end event on the internal temperature 

Out.S 

Start event on the external temperature 

Out.E 

End event on the external temperature 

dIF.S 

Start event on the temperature difference 

dIF.E 

End event on the temperature difference 

Fourth row 

[d][d].[d] 

1

 

For the start event, the number indicates the measured temperature when a start event 
is detected 
For the end event, the number indicates the maximum temperature measured during 
the event interval. 

1. d 

 decimal number 

 

Users can check the event occurrence time(year, month, day, time, hour, minute, second, and millisecond) 

for each event by pressing the down[

] button on each event screen. 

 

Fig 4.2 Event Occurrence Time 

 

 

 

First row   

Year 

Second row 

Month, day 

Third row 

Hour, minute   

Fourth row

 

Second, millisecond 

 

 

 

 

 

Содержание Accura 2350-TEMP

Страница 1: ......

Страница 2: ...have received appropriate training for high voltage and current devices Caution If hazardous voltages are mishandled while installing and operating the product in the field it can cause serious injur...

Страница 3: ...tions and the manual before making orders In the absence of written agreements Rootech Inc assumes no liability for applications assistance customer s system design or infringement of patents or copyr...

Страница 4: ...or the product Rootech will decide at its discretion whether to repair or replace it or give a refund for the product for when the warranty period for the product expired or issues related to the prod...

Страница 5: ...iginal purchaser is responsible for determining the feasibility of such suggestions and should conduct tests to prove their feasibility It is the original purchaser s responsibility to determine the s...

Страница 6: ...Added the SYSTEM setup item Separated the RJ45 cable from the RJ12 cable 1 11 December 1 2021 Changed the image and the text on the cover page as well as the number of Accura TSEN devices that can be...

Страница 7: ...th Accura TSEN using the Communication Cable 16 Chapter 2 Accura TSEN Operation Setup 17 Power Supply 17 ID Setup 17 RESET Button 18 Communication 18 LED Status Indicators 18 Temperature Measurement 1...

Страница 8: ...Screen Composition 28 EVENT Setup 30 DIO Setup 31 INTERFACE Setup 32 SYSTEM Setup 33 EVENT Mode 34 Screen Composition 34 Chapter 4 Accura 2300 S Operation Setup 36 Display Mode of Accura 2300 S 36 Ev...

Страница 9: ...350 TEMP on the Panel 13 Fig 1 10 Hole Dimensions for Mounting Accura 2350 TEMP on the Panel 13 Fig 1 11 Connection between Accura 2350 TEMP and Accura 2300S using the Communication Cable 14 Fig 1 12...

Страница 10: ...erved Chapter 1 Installation and Wiring Before Installation Product Appearance Fig 1 1 Accura 2350 TEMP Accura 2350 TEMP Front Accura 2350 TEMP Rear Accura 2350 TEMP Side Fig 1 2 Accura TSEN Component...

Страница 11: ...1 Installation and Wiring 2020 Rootech Inc All Rights Reserved Page 11 Fig 1 4 Accura TSEN Components Accura TSEN device Mounting wings screws Dimensions Fig 1 5 Accura 2350 TEMP Front Fig 1 6 Accura...

Страница 12: ...ment in the distribution panel Accura 2300 S and Accura 2350 TEMP devices are installed at the front of the distribution panel and multiple Accura TSEN devices are installed inside the distribution pa...

Страница 13: ...2350 TEMP module into the panel cutout Fit the mounting wheel into the screw thread at the back of Accura 2350 TEMP Turn the mounting wheel to the right and fix Accura 2350 TEMP to the panel You can...

Страница 14: ...d Connection with Accura 2300 S using the Communication Cable Connect the RJ12 6C communication cable to the RJ12A RJ12B port Accura 2350 TEMP receives power from Accura 2300 S via the RJ12 6C communi...

Страница 15: ...holes of the device s mounting wings into the mounting holes of the panel Fix Accura TSEN to the panel using the screws Fig 1 12 Mounting Accura TSEN on the Panel DIN Rail Mounting Fit the bottom por...

Страница 16: ...ved Connection with Accura TSEN using the Communication Cable Connect the Ethernet communication cable to the RJ45A RJ45B port Accura TSEN receives power from Accura 2350 TEMP via the RJ45 Ethernet co...

Страница 17: ...erature measurement allowing for the overall temperature monitoring in the distribution panel For details about how to connect Accura TSEN devices using the daisy chain method refer to Chapter 1 Insta...

Страница 18: ...id Copper CAT 5e FTP F UTP 1 Communication cable length Up to 25 m 1 FTP F UTP Foiled Shield Twisted Pair LED Status Indicators In normal operation the LED on the Accura TSEN device blinks green When...

Страница 19: ...ions of the distribution panel It allows for the overall temperature control of the distribution panel Users can check data on measured temperatures and set up events related to the temperatures on th...

Страница 20: ...tems and change it EVENT mode Displays detailed event data LED Status Indicators Item Color Description POWER Green It is turned on when the device is powered on EVENT Red It blinks red when an event...

Страница 21: ...r type RJ45 connector Protocol RS 485 based internal protocol RESET Button It is used to reset external temperature events on the Accura 2350 TEMP module Users can also reset event alarms by enabling...

Страница 22: ...ated mechanical relay type DO channel Form A It gives users notifications through the DO when an event occurs Item Description Port name DO DOG Mechanical Relay Form A Connector type Screw type termin...

Страница 23: ...ured at multiple locations in the distribution panel Accura TSEN has the same sensor as Accura 2350 TEMP and refer to the above table for the detailed information on the temperature sensor of Accura T...

Страница 24: ...emperatures with the RESET button on the back of the Accura 2350 TEMP module Users can also reset events with the Digital Input and the EVENT button on the Accura 2350 TEMP module Those buttons are in...

Страница 25: ...Column 4 Column 5 Column 6 SUMMARY IN TSEN 1 1 IN TSEN 2 1 OUT DIGITAL IO SYSTEM 1 The IN TSEN column is added as the number of the installed Accura TSEN devices increases Item Description Now temper...

Страница 26: ...ture measured by each Accura TSEN device inside the distribution panel OUT 2 Indicates the temperature measured at the front of the distribution panel where the Accura 2350 TEMP module is installed 1...

Страница 27: ...during the trend interval 1 It is the average temperature measured during the trend interval DIGITAL IO Column It indicates the digital input output status of the Accura 2350 TEMP module Screen Descr...

Страница 28: ...Screen Composition Each column supports EVENT DIO INTERFACE SYSTEM settings Full Screen Column 1 Column 2 Column 3 Column 4 EVENT SETUP DIO SETUP INTERFACE SETUP SYSTEM Button Operation Button Descri...

Страница 29: ...he setup of numbers 6 Long press 6 Save the changed value of the setup item temporarily the screen stops blinking and return to the Selection mode If there is another setup item go back to step 3 and...

Страница 30: ...n panel Screen Setup Item Range Default Function Disable Enable Disable Threshold 0 100 32 0 212 0 40 Time Delay 0 10 sec 0 sec DO Disable Enable Disable DIFF It indicates the setup for events on temp...

Страница 31: ...Item Range Default DI Disable the reset function is disabled Event LED the function to reset the Event LED is enabled DO the function to reset the DO is enabled Both the function to reset the Event L...

Страница 32: ...occurs when the DO contact is closed Reverse mode 0 The contact point remains closed 1 Pulse occurs when the DO contact is open Normal Pulse Period Pulse cycle time for Pulse Type 0 2 9 9 sec 1 0 sec...

Страница 33: ...the pulse period the device gives users intermittent beeping sound However when the Pulse On time is same as or longer than the pulse period it provides users with continuous sound Setup Exit Screen S...

Страница 34: ...g data on temperatures and the Column 3 DIO EVENT screen shows event log data on the DI DO Temperature events include start and end events The end event on temperatures provides data on the highest te...

Страница 35: ...en with the up down and left right buttons Long press 2 Enter the EVENT mode EVENT Mode Short press Select the Event column with the left right buttons Short press Select the Event screen with the lef...

Страница 36: ...ption Display mode Displays the measured values of the selected Accura 2350 module ID Setup mode Supports setup for various parameters of Accura 2300 S 2350 modules network wiring PT communication eve...

Страница 37: ...Accura 2350 TEMP module by pressing the right or left button on the Accura 2300 S screen and moving to the MODULE column When multiple Accura 2350 TEMP modules are connected to the Accura 2300 S devi...

Страница 38: ...Accura 2300 S device and entering the event log mode However users cannot reset event notification settings on the Accura 2350 TEMP module with the button on the Accura 2300 S device Setup Mode of Acc...

Страница 39: ...econd row M tMP Displays the module where the event occurred TEMP module Third row In d 1 S Accura TSEN d the start event on the internal temperature In d 1 E Accura TSEN d the end event on the intern...

Страница 40: ...cond and millisecond for each event by pressing the down button on each event screen Fig 4 3 DI Event Screen Event on Closed Contact Point Event on Open Contact Point The DI DO event screen indicates...

Страница 41: ...nnect Accura 2350 TEMP with Accura TSEN Connector type RJ45 connector RJ45 Ethernet cable Protocol RS 485 based internal protocol Connection with Accura TSEN devices Accura 2350 TEMP can be connected...

Страница 42: ...tion cable Ethernet cable 24 AWG Solid Copper CAT 5e FTP F UTP 1 Cable length Up to 25 m Accura TSEN ID ID that enables communication 1 6 Standby ID 0 factory default value communication unavailable C...

Страница 43: ...Accura 2350 TEMP User Guide Appendix B Ordering Information 2020 Rootech Inc All Rights Reserved Page 43 Appendix B Ordering Information Model Name Accura 2350 TEMP Accura TSEN...

Страница 44: ...500 are trademarks of Rootech Inc Contact us for detailed product specifications and ordering information Information contained herein is subject to change without notice Copyright Rootech Inc Printed...

Отзывы: