Chapter 3 Accura 2350 Operation/Setup
Accura 2300/2350 User Guide
Page 98
ⓒ
2011 Rootech Inc. All Rights Reserved
Setup Mode
Setup Menu
Each time SET button is pressed briefly, the setup menu is selected in the following sequence.
ID
Phase Seq.
/ Load
direction
Load
connect
-ion
Load
phase
selection
CT ratio
1
0/1K
CT ratio
1
1-999
Rating
Current
LCD
Display
Direction
Leakage
Current
Leakage
Current
Event
2
1. It is displayed only on Accura 2350-3P-CT5A-75/Accura 2350-3PSC-CT5A-90 model using external CT. The CT ratio can
be set from 1 - 1999 using "0/1k" setup screen and "1-999" setup screen.
2. This is the leakage current event setup screen that is displayed only when the leakage current threshold is set in the
leakage current measurement setup screen.
Note
If there is no button operation for 10 seconds in setup mode, it automatically returns to display mode.
If there is no button operation for 25 seconds in setup change mode, it automatically returns to display mode
ID Setup
Item
Range
Description
ID
[d][d]
1
Module ID
2
Setup
0 - 39[default 255]
1. d
decimal number.
2. Module ID is divided as follows. All Accura 2350s are factory-assigned as Standby ID by default.
Module ID
ID
Description
Communication ID
ID 0 - 39
Able to communicate with Accura 2300.
Conflict ID
ID duplication Two or more IDs are the same Module ID, unable to communicate.
Standby ID
ID 255
Module ID for connection status recognition, unable to communicate.
Note
You can manually assign Accura 2350's Module ID with SET button, but you can automatically assign the
Module ID to all Accura 2350s connected to Accura 2300 by using "Module ID Auto Assignment" setup on
Accura 2300.