Accura 2300/2350 User Guide
Chapter 4 Accura 2300 Operation/Setup
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 177
Event Log Mode
Start Event and End Event
Accura 2300 generates a start event when the event condition is satisfied when the power quality event such
as Dip[Sag], Swell, Fuse Fail is set, and generates the end event when the event is restored to the normal state.
All events except digital input [DI] event are always composed of start event and end event.
Start Event Alarm Generation
When the start event and the DI event occur, the event log is processed and a start event alarm is generated.
When start event alarm occurs, LCD backlight and the EVENT LED on the lower left blink. When the dip/swell
start event occurs, the Dip/Swell segment on the top bar blinks.
When the end event occurs, only the event log is processed and no alarm is generated.
The maximum 100 event logs are displayed.
Note
-
Event LCD backlight illumination time can be set to clear the LCD backlight blinking, which indicates the
start event generation, to be cleared when the event log is confirmed, or to be maintained until 9999
minutes.
-
It is possible to eliminate the EVENT LED blinking that notifies the generation of the start event by the
setting of the event LED illumination time when the event log is confirmed, or to maintain it until 9999
minutes.
Fig 4.26 Dip[Sag] Event Alarm Display
Fig 4.27 Swell Event Alarm Display
Start Event Alarm Clearing
When an alarm occurs, the long press of EVENT button to enter the event log mode clears the event alarm. In
the event log mode, you can check the recent 100 event logs in detail.