Chapter 4 Accura 2300 Operation/Setup
Accura 2300/2350 User Guide
Page 168
ⓒ
2011 Rootech Inc. All Rights Reserved
Digital Input/Output Setup
If RS485 option is selected when ordering Accura 2300, setup column for digital I/O is not supported because
digital I/O terminal is replaced by RS-485 communication terminal.
Digital Input Status
Setup range
Description
“_”
Open contact display
“
ㅁ
”
Closed contact display
Simultaneously display the status of channel 1 and channel 2 from the left.
Digital Output Type
Setup range
Description
Latch[default]
1
Latch type
PuLS.U
1
Uncountable pulse type
2
PuLS.C
1
Countable pulse type
2
P.PuLS
1
Periodic pulse type
2
1. The operation for digital output type is as follows.
2. Pulse is defined as a pulse period and a pulse on time.
Output type
Command
Operation
3
Latch
1
Maintain Closed contact.
0
Maintain open contact.
Uncountable pulse
1
Pulse generation of single closed contact. After the pulse is generated, the
command is automatically cleared.
Additional commands entered within the pulse period are ignored.
0
Not used(Command is auto-cleared)
Countable pulse
1
Pulse generation of single closed contact. After the pulse is generated, the
command is automatically cleared.
Additional commands entered within the pulse period are generated an
additional number of times after the end of the pulse period.
0
Not used(Command is auto-cleared)
Periodic pulse
1
Pulse of closed contact is generated continuously while the command is 1.
0
Pulse generation of closed contact is stopped after completion of the
pulse.
3. Explanation of the case where the output polarity setup is "normal". If "Reverse" is selected, the operation of the
closed contact and the open contact is reversed.