Dip End Voltage
Dip end voltage is configured as percentage to reference voltage. Dip end event is generated when measured
voltage returns above the end voltage. Hysteresis voltage exists between start voltage and end voltage to
prevent a large number of short events and minimum Hysteresis is 1%. In other words, end voltage can be
configured at least 1% higher than start voltage. If start voltage is configured higher than end voltage, end
voltage is automatically reconfigured 1% higher than start voltage.
Setup range
Description
2.0 - 99.0% [default 92.0%]
Percentage of Dip reference voltage
Dip end voltage display
VL-N [Line-to-neutral]
3P4W/1P3W/1P2W connection
VL-L[Line-to-line]
3P3W connection
[d][d][d].[d] V/kV
Dip reference voltage * Percentage
Fig 4.22 Dip Event Setup[3-phase 4-wire]
Reference voltage: Line-to-line voltage
380V setting
Fig 4.23 Dip Event Setup[3-phase 3-wire]
Reference voltage: Line-to-line voltage
380V setting