Accura 2300/2350 User Guide
Chapter 4 Accura 2300 Operation/Setup
ⓒ
2011 Rootech Inc. All Rights Reserved
Page 135
Demand
Detailed information for demand power and demand current is displayed by repressing Right[>] button at
power screen. First screen of demand column displays demand active power for each phase and total. And
demand current, peak[maximum] demand active power and peak[maximum] demand current are sequentially
displayed by pressing Down[
v
] button. These are sequentially displayed in the reverse order by pressing
Up[^] button.
Fig 4.13 Demand Active Power Display Screen
Active Energy
Detailed information for energy is displayed by repressing Right[>] button at demand screen. First screen of
energy column displays net energy. And received energy, delivered energy, and total energy are sequentially
displayed by pressing Down[
v
] button. These are sequentially displayed in the reverse order by pressing
Up[^] button. Net energy is the value obtained by subtracting delivered energy from received energy, and
sum power is the sum of received energy and delivered energy.
Fig 4.14 Net Energy Display Screen
Leakage Current
Leakage current measurement is supported by installing an external ZCT[voltage-type] and connecting the
ZCT output voltage to the ZCT input terminal of Accura 2350 module. Leakage current measurement is
supported only at the module that the leakage current measurement is activated. If the leakage current
threshold value of Accura 2350 is configured as non-zero value, leakage current measurement is activated. At
this screen, measured leakage current of the selected module can be observed by selecting the module ID at
left-top.
Pressing Right[>] button on energy screen displays the measured leakage current for the module with leakage
current measurement enabled in Accura 2350. The module ID of the top bar is one of the module IDs for