MTS WIRING DIAGRAM

Utilizing a portable generator, your Manual Transfer Switch 
will power to selected circuits in the event that utility power 
is interrupted. The MTS normal operation is to connect 
the Utility to the selected circuits using the internal Load 
Subpanel. The MTS system can manually switch up to 8 AC 
circuits when operating on generator power. MTS301SYS 
and MTS501SYS systems monitors and displays power 
being consumed by the selected circuits, using Light Emitting 
Diodes (LED’s), to allow the home owner to manually control 
the loads on the generator. A survey of power usage of the 
selected circuits should be performed to achieve the desired 
performance from the portable generator.

After unpacking inspect the Manual Transfer Switch for any 
damage that may have occurred during shipping. If any 
missing parts or damage is discovered when unpacking, 
do not return the unit to the place of purchase; please 
contact Ronk Electrical Industries, Inc. Technical Services 
for instructions on how to proceed. Never install a Manual 
Transfer Switch that has been damaged.

The MTS enclosure is NEMA type 3R rated and is suitable for 
indoor or outdoor installations.  
Guidelines for mounting the unit include:
•   Ensure that mounting surface can support the 25 pound 

weight of the MTS and adheres to all local codes

•   The enclosure must be installed with NEMA type 3R 

hardware and connections

•   Level and plumb the unit enclosure to prevent deformation
•   Never install the MTS where any corrosive substance may 

come in contact with the enclosure

•   Protect the MTS at all times against excessive moisture, 

dust, dirt, lint, construction grit and corrosive vapors

•   An optional inlet box can be used to permit installing the 

generator outside while installing the MTS inside next to the 
Main distribution panel/ load center

UNPACKING AND HANDLING

Figure 1 –  Manual Transfer Switch Diagram

The schematic shows the internal wiring of 
the MTS with the Manual Transfer Switch 
Indicator Printed Circuit Board (MTSI PCB) 
assembly. The MTSI PCB uses 2 current 
transformers to acquire power for the 
monitoring circuitry and to measure power 
in each line of the input power. Each circuit 
being monitored must have the circuit wire 
pass through the A or B current transformer. 
If this is not done the monitoring will not 
function. If additional circuits are added 
to the MTS, make sure that the wire to the 
new circuit breaker is passed through the 
appropriate current transformer.

Содержание MTS301

Страница 1: ...ONK PO Box 160 106 East State Street Nokomis IL 62075 0160 Toll Free 800 221 7665 ronkelectrical com MANUAL TRANSFER SWITCH 30 50 AMP Owner s Installation Manual Model MTS301SYS MTS301 MTS501SYS MTS50...

Страница 2: ...s to explain and or exemplify a product service or maintenance improvement We reserve the right to make any change at any time without notice Some images may vary depending upon which model is shown A...

Страница 3: ...ntents 10 Unpacking and Handling 11 MTS Wiring Diagram 11 Installation Diagram 12 FUNCTIONAL TESTING 13 Electrical 13 MOUNTING DIMENSIONS 14 SET UP 15 GENERATOR CAPACITY DISPLAY LEARN FUNCTION 15 SETT...

Страница 4: ...ment is supplied with this combined Owner s and Installation Manual This is an important document and should be retained by the owner after the installation has been completed Every effort has been ma...

Страница 5: ...nicate effectively with your licensed electrician and familiarize yourself with the installation options available The equipment warranty is void unless the system is installed by a licensed electrici...

Страница 6: ...rious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE addresses practices not related to personal injury The manufacturer of this pr...

Страница 7: ...mod r es AVIS pratiques les adresses ne sont pas li s des blessures Le fabricant de ce produit ne peut pas raisonnablement anticiper toutes les circonstances potentielles pouvant comporter un danger L...

Страница 8: ...alert at all times while working on this equipment Never work on the equipment when you are physically or mentally fatigued If connected devices overheat turn them off and turn off their circuit brea...

Страница 9: ...ous travaillez sur cet quipement Ne jamais travailler sur l quipement si vous tes fatigu physiquement ou mentalement Si les appareils branch s sont en surchauffe teignez les et mettez leur disjoncteur...

Страница 10: ...X X X X X MTS301SYSL1C X X X X X X X MTS301SYSL2C X X X X X X X RONK 50A MANUAL SWITCH OPTIONS 100A Utility Breaker 50A Generator Breaker 6 Branch Breakers 6 Wiring harness Included 50A Inlet Installe...

Страница 11: ...S enclosure is NEMA type 3R rated and is suitable for indoor or outdoor installations Guidelines for mounting the unit include Ensure that mounting surface can support the 25 pound weight of the MTS a...

Страница 12: ...anced on each phase of the generator to achieve optimum generator performance When on generator power the home owner must monitor the loads to prevent stalling the generator due to an overload Changes...

Страница 13: ...lluminated verify that the circuit has a load attached to the circuit Turn on circuit breaker B2 and verify that the lower right LED is illuminated If the LED is not illuminated verify that the circui...

Страница 14: ...14 Ronk Manual Transfer Switch Owner s and Installation Manual MOUNTING DIMENSIONS Figure 3 Mounting Dimensions...

Страница 15: ...g used it will only display 100 when the power passing through the switch is at 10kw or 41 6 Amperes Setting the capacity of the generator is the responsibility of the installer or the operator There...

Страница 16: ...MTS by shutting off Circuit Breaker A1 B1 2 Turn off all load circuit breakers A2 through B3 and A5 through B6 3 Plug in the portable generator start the generator and turn on A4 B4 4 Turn on Circuit...

Страница 17: ...kers are turned on If the LED s are not balanced then rewire the loads to balance the load on the generator NORMAL OPERATION As each circuit breaker is turned on the LED display should be examined to...

Страница 18: ...roved by the manufacturer or registrant of this equipment can void your authority to operate this equipment under Federal Communications Commission rules In order to maintain compliance with FCC regul...

Страница 19: ...tion 3 The warranty starts as of the original purchase date by the first retail consumer when the unit is registered if not registered the warranty start date defaults to the manufacture date ABOUT YO...

Страница 20: ...T SHOWN 301 COVER PLATE Z1169935 501 COVER PLATE Z1169937 FRONT HINGE SCREWS Z1000062 RISER TO BACK SCREW Z1000183 DEADFRONT TO BACK SCREW Z1001290 GROUND CONN TO BACK SCREW Z1002772 C B STAB ASSY TO...

Страница 21: ...GEN UTIL Amperage 30 60 50 100 Phase Single Limited Warranty 4 Years Circuits Partial House 8 circuit s maximum Amps 30 50 Service entrance disconnect YES Maximum Load Current YES Rated AC VoltageA 1...

Страница 22: ...A near max Phase A near max both phases are using more power than generator can provide both phases are using more power than generator can provide Try to move some loads from A B to Balance the Gener...

Страница 23: ...e generator is over capacity Q The GFCI trips on the Generator every time I switch to it A Your generator needs to be converted from portable mode to permanent or installed mode Consult your generator...

Страница 24: ...RONK PO Box 160 106 East State Street Nokomis IL 62075 0160 Toll Free 800 221 7665 ronkelectrical com MANUAL TRANSFER SWITCH UG 004_2 2019...

Отзывы: