background image

10 

RONK Automatic Transfer Switch Owner’s Manual

INSTALLATION & WIRING

GENERAL INFORMATION

All RONK Automatic  transfer switches are factory-tested and 
approved. Installation requires the mounting of the transfer 
switch and external wiring for utility and generator operation. 
Once the transfer switch is properly installed, it should be 
visually inspected and approved before any testing is performed.

MOUNTING LOCATION

All RONK Automatic transfer switches require that adequate 
lifting means be used to install the switch at its mounting 
location. Be certain to choose a location that offers a flat 
mounting surface that can support the transfer switch. Caution 
must be taken at the installation site to make sure the site is 
free from excessive moisture, fluctuating temperature ranges, 
dust, corrosive materials, etc. Before any drilling takes place, be 
certain the drilling area is free of any hazards including electrical 
wiring, piping, etc. Extreme caution  should be exercised when 
any installation and drilling are performed to protect the transfer 
switch from any debris including contaminants, filings, etc. 
Any debris within the transfer switch may result in a system 
malfunction.

!

WARNING

Always use adequate lifting to lift and mount the 
transfer switch during installation.

MODEL

POLES

AMPS

MAX VOLTS

ANY CB MAX DURATION

SPECIFIC CB*

MANUFACTURER

TYPE

RATING

V12

V13

1

3

100

240

10 kA

0.025 Seconds

22 kA

Siemens

HED4, HED6

125 A

Siemens

ED4, ED6

125 A

Siemens

CED6

125 A

Eaton / Cutler Hammer

FDC

150 A

Eaton / Cutler Hammer

QCHW

125 A

Eaton / Cutler Hammer

FCL

100 A

Eaton / Cutler Hammer

FB

100 A

SQUARED D

FI

100 A

V22

1

200

240

10 kA

0.025 Seconds

22 kA

Siemens

FXD

250 A

Siemens

NFK

250 A

SQD/Schneider

QBL

250 A

General Electric

SFHA

250 A

V23

3

200

240

10 kA

0.025 Seconds

25 kA

General Electric

SFH

250 A

W04

1

3

400

480

NA

NA

10 kA

Cutler-Hammer

LD

600 A

N06

1

3

600

480

NA

NA

12 kA

Cutler-Hammer

MD

800 A

SHORT CIRCUIT WITHSTAND/CLOSING RATINGS, ANY CIRCUIT BREAKER (ANY CB) 

When protected by a circuit breaker, this transfer switch is suitable for use in a circuit capable of delivering the short-circuit current for 

the maximum time duration and voltage marked below.

SPECIFIC CIRCUIT BREAKER MANUFACTURER AND TYPE (SPECIFIC CB) 

When protected by a circuit breaker of the specific manufacture, type, and ampere rating as marked below, this transfer switch is 

suitable for use in circuits capable of delivering the short-circuit current at the maximum voltage marked.

MOUNTING REQUIREMENTS

The enclosure has a NEMA (National Electrical Manufacturer’s 
Association) Type 4 rating and is suitable for indoor/outdoor 
installations and provides a degree of protection against falling 
rain and sleet. Guidelines for mounting the unit include:

• Ensure that the mounting surface can support the weight of the 

switch and adheres to all local codes.

• The enclosure must be installed with NEMA Type 4 hardware 

and connections.

• Level and plumb the unit enclosure to prevent deformation.

• Never install the switch where any corrosive substance may 

come in contact with the enclosure.

• Protect the switch at all times against excessive moisture, dust, 

dirt, lint, construction grit and corrosive vapors. 

Содержание 100-600 AMP

Страница 1: ...OWNER S INSTALLATION MANUAL 100 600 AMP RONK Automatic Transfer Switch...

Страница 2: ...plain and or exemplify a product service or maintenance improvement We reserve the right to make any change at any time without notice Some images may vary depending upon which model is shown ALL RIGH...

Страница 3: ...e 8 SPECIFICATIONS 9 RONK ATS 100A 200A 400A 600A Specifications 9 INSTALLATION AND WIRING 10 General Information 10 Mounting Location 10 Mounting Requirements 10 Recommended Upstream Protection 11 Po...

Страница 4: ...anual Transfer 21 400A Manual Transfer 21 600A Manual Transfer 22 MAINTENANCE 23 Recommended Maintenance 23 Maintenance 23 DRAWINGS 24 100A 200A 240V Schematic 24 400A 240V Schematic 25 400A 480V Sche...

Страница 5: ...efore use Refer to the installation section of this manual for instructions on installation procedures Only licensed electrical contractors should install an ATS Installations must comply completely w...

Страница 6: ...ion in the manner intended The manufacturer of this product cannot reasonably anticipate every possible circumstance that might involve a hazard The warnings in this manual and the tags and decals aff...

Страница 7: ...ocution Do not touch bare wires Do not use equipment with worn frayed bare or otherwise damaged wiring Do not handle electrical cords while standing in water while barefoot or while hands or feet are...

Страница 8: ...the enclosure Care should be taken to always protect the equipment from impact Do not remove the protective packaging until the equipment is at the installation site and ready to be installed A shipp...

Страница 9: ...x 6 ATS40012 W04 1 400 240 181 lbs 48 x 30 x 10 ATS40014 W04 1 400 480 203 lbs 48 x 30 x 10 ATS40032 W04 3 400 240 188 lbs 48 x 30 x 10 ATS40034 W04 3 400 480 210 lbs 48 x 30 x 10 ATS60012 N06 1 600...

Страница 10: ...er FDC 150 A Eaton Cutler Hammer QCHW 125 A Eaton Cutler Hammer FCL 100 A Eaton Cutler Hammer FB 100 A SQUARED D FI 100 A V22 1 200 240 10 kA 0 025 Seconds 22 kA Siemens FXD 250 A Siemens NFK 250 A SQ...

Страница 11: ...an the circuit breakers with the recommended ratings given above may cause improper operation of the switch WARNING Low voltage wire cannot be installed in the same conduit as power voltage wiring It...

Страница 12: ...he remote start stop connections of the generator to allow automatic starting These are N O dry contacts 8A 35 Vdc Max An optional customer supplied test switch may be installed by the customer using...

Страница 13: ...s automatic start controller When the ATS controller senses that the generator has started and is within acceptable limits the transfer switch will wait until the utility to generator time delay Para...

Страница 14: ...me and day when the battery is re applied SCHEDULER The DSE331 scheduler is the feature that sets the exercise timer for the Automatic Transfer Switch and the generator set The ATS comes from the fact...

Страница 15: ...e 240V switches are usable on 208V systems See manual for instructions to change parameters TIME DELAY FUNCTION SETTING LINE Transient 2 Seconds Engine Start 13 Seconds Transfer LINE to AUXILIARY 21 S...

Страница 16: ...provides a quick start guide to the module s operation for DSE controller 331 MODE SELECTION OPERATION NOTE For further details see the section entitled MODE SELECTION elsewhere in this manual Press...

Страница 17: ...LCD display until the user selects a different page or after an extended period of inactivity the module will revert to the status display When scrolling manually the display will automatically return...

Страница 18: ...ch Owner s Manual QUICKSTART GUIDE INSTRUMENTATION The instrumentation page contains the following information S1 Voltage L N S1 Voltage L L S1 Frequency S2 Voltage L N S2 Voltage L L S2 Frequency Bat...

Страница 19: ...Switch Fail Alarm The Switching device has failed to operate Failed to Start The engine has not fired after the preset number of start attempts Failed to Stop The module has detected a condition that...

Страница 20: ...mode is used to provide an over ride function to prevent the controller from starting the generator in the event of a remote start S1 out of limits condition occurring Prohibit return This mode is use...

Страница 21: ...ovable lever handle is used to transfer the mechanism The transfer switch is in the utility position when reference A on the contactor is set to the ON position and reference B is set to the OFF posit...

Страница 22: ...h Trip using an object such as a screwdriver to open the utility poles 2 Set the removable handle on M and operate in the UP direction while pushing select with the screwdriver To transfer from Genera...

Страница 23: ...ation for possible safety hazards Inspect mounting location for any safety or fire hazards Inspect for dirt wiring damage and mechanical damage Inspect the transfer switch for loose hardware Check all...

Страница 24: ...24 RONK Automatic Transfer Switch Owner s Manual WIRE DIAGRAM DRAWINGS 100A AND 200A SCHEMATIC Source 1 LINE Utility Source 2 AUXILIARY Generator...

Страница 25: ...RONK Automatic Transfer Switch Owner s Manual 25 WIRE DIAGRAM DRAWINGS 400A 240V SCHEMATIC Source 1 LINE Utility Source 2 AUXILIARY Generator...

Страница 26: ...26 RONK Automatic Transfer Switch Owner s Manual WIRE DIAGRAM DRAWINGS 400A 480V SCHEMATIC Source 1 LINE Utility Source 2 AUXILIARY Generator...

Страница 27: ...RONK Automatic Transfer Switch Owner s Manual 27 WIRE DIAGRAM DRAWINGS 600A 240V SCHEMATIC Source 1 LINE Utility Source 2 AUXILIARY Generator...

Страница 28: ...28 RONK Automatic Transfer Switch Owner s Manual WIRE DIAGRAM DRAWINGS 600A 480V SCHEMATIC Source 1 LINE Utility Source 2 AUXILIARY Generator...

Страница 29: ...licable For example warranty service would not apply if equipment damage occurred because of misuse lack of routine maintenance shipping handling warehousing or improper installation Similarly the war...

Страница 30: ...30 RONK Automatic Transfer Switch Owner s Manual NOTES...

Страница 31: ...RONK Automatic Transfer Switch Owner s Manual 31...

Страница 32: ...106 E State Street Nokomis IL 62075 800 221 7665 www ronkelectrical com...

Отзывы: