0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 ms.

 

RS485 Output for Modbus RTU

For Modbus RTU, the following RS485 communica

-

tion parameters can be configured from the set-up 

menu:
Baud rate 2400, 4800, 9600, 19200, 38400

Parity none (default) / odd / even

Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 1 to 247
Modbus™ Word order Hi/Lo byte order is set auto

-

matically to normal or reverse. It cannot be config-
ured from the set-up menu.

Energy Measurements

Imported/Exported active energy 

0 to 9999999.9 kWh

Imported/Exported reactive energy

0 to 9999999.9 kVArh 

Total active energy

0 to 9999999.9 kWh

Total reactive energy 

0 to 9999999.9 kVArh

Auxiliary Supply

Two-way fixed connector with 2·5mm2 stranded wire 
capacity. 85 to 275V a.c. 50/60Hz ±10% or 120V to 
380V d.c. ±20%. Consumption <2W 10VA.

Operating range

87...275VAC ±10% / 120....380VDC 
±20%

Measured Inputs

Voltage inputs through 4-way fixed connector with 
2.5mm² stranded wire capacity. single phase two 
wire(1p2w), three phase three wire(3p3w) or three 
phase four wire(3p4w) unbalanced. Line frequen

-

cy measured from L1 voltage or L3 voltage. Three 
current inputs (six physical terminals) with 2.5mm² 
stranded wire capacity for connection of external CTs. 
Nominal rated input current 5A or 1A a.c. Rms.

Nominal Voltage Input

(Ph+N) 100 to 289V (Ph+Ph) 173 
to-500V

Max Continuous Voltage

120% of nominal

Nominal Input Current

0.25-5A(6)A AC rms

Max Continuous Current

120% of nominal

Nominal Input Current Burden

0.5VA

Frequency

45-65Hz

Product Datasheet

Accuracy

Voltage

0·5% of range maximum

Current

0·5% of nominal

Frequency  

0·2% of mid-frequency

Power factor     

1% of unity (0.01)

Active power (W) 

±1% of range maximum

Reactive power (VAr)  

±1% of range maximum

Apparent power (VA) 

±1% of range maximum

Active energy (Wh)  

Class 1 IEC 62053-21

Reactive energy (VARh) 

±1% of range maximum

Total harmonic distortion

1% up to 31st harmonic

Response time to step input  

1s, typical, to >99% of final 
reading, at 50 Hz.

Reference Conditions of Influence Quantities

Influence Quantities are variables that affect measure-
ment errors to a minor degree. Accuracy is verified 
under nominal value (within the specified tolerance) 
of these conditions.

Ambient temperature 

23°C ±1°C

Input waveform  

50 or 60Hz ±2%

Input waveform 

Sinusoidal (distortion factor < 
0·005)

Auxiliary supply voltage

Nominal ±1%

Auxiliary supply frequency

Nominal ±1%

Auxiliary supply waveform (if AC) 

Sinusoidal (distortion factor < 0·05)

Magnetic field of external origin

Terrestrial flux

Environment

Operating temperature 

-25°C to +55°C*

Storage temperature

-40°C to +70°C*

Relative humidity 

0 to 95%, non-condensing

Altitude  

Up to 3000m

Warm up time

1 minute

Vibration 

10Hz to 50Hz, IEC 60068-2-6, 2g

Shock 

30g in 3 planes

*Maximum operating and storage temperatures are 

in the context of typical daily and seasonal variation.

Version No. 1.0     18/03/2015