16. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is recommended good practice that all refrigerants are recovered
safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case
analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is
available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c)
Before attempting the procedure, ensure that:
•
mechanical handling equipment is available, if required, for handling refrigerant cylinders;
•
all personal protective equipment is available and being used correctly;
•
the recovery process is supervised at all times by a competent person;
•
recovery equipment and cylinders conform to the appropriate standards.
d)
Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various
parts of the system.
f)
Make sure that cylinder is situated on the scales before recovery takes place.
g)
Start the recovery machine and operate in accordance with instructions.
h)
Do not overfill cylinders (no more than 80 % volume liquid charge).
i)
Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)
When the cylinders have been filled correctly and the process completed, make sure that the
cylinders and the equipment are removed from site promptly and all isolation valves on the
equipment are closed off.
k) Recovered refrigerant shall not be charged into another
refrigerating system
unless it has
been cleaned and checked.
17. Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The
label shall be dated and signed. For appliances containing
flammable refrigerants
, ensure that there
are labels on the equipment stating the equipment contains
flammable refrigerant
.
18. Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total system
charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled
for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete
with pressure-relief valve and associated shut-off valves in good working order. Empty recovery
cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the
equipment that is at hand and shall be suitable for the recovery of all appropriate refrigerants
including, when applicable,
flammable refrigerants
. In addition, a set of calibrated weighing scales
shall be available and in good working order. Hoses shall be complete with leak-free disconnect
couplings and in good condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery
Содержание R-91110
Страница 8: ...R 91110 True Ion GR 1 R 91110 True Ion Air Purifier...
Страница 9: ...R 91110 True Ion GR 2 52 g...
Страница 11: ...R 91110 True Ion GR 4 8 8 8...
Страница 12: ...R 91110 True Ion GR 5...
Страница 13: ...R 91110 True Ion GR 6 5 32 C 16 32 C 20 cm 50 cm...
Страница 14: ...R 91110 True Ion GR 7 1 2 3 4 5 6 7 1 1 2 2 3 3 4 4 5 5 6 6 7 7 ON OFF ON OFF DRY CLOTHES...
Страница 15: ...R 91110 True Ion GR 8 Auto 5 5 5 30 80 1 24...
Страница 16: ...R 91110 True Ion GR 9 3 AY...
Страница 17: ...R 91110 True Ion GR 10 9 mm 60 cm...
Страница 18: ...R 91110 True Ion GR 11 10 cm HEPA HEPA...
Страница 19: ...R 91110 True Ion GR 12 HEPA 1 HEPA DF 028 Probl m o o 5 C 32 C...
Страница 20: ...R 91110 True Ion GR 13 FL E2 P1 220 240 V 50 Hz 145 W 2 l 5 32 C R290...
Страница 21: ...R 91110 True Ion GR 14...
Страница 22: ...R 91110...
Страница 23: ...ureda Prohibition...
Страница 24: ...Q Q 5 32 5 32 30 80 16 32 Q...
Страница 25: ...50 20 4 Minimum 50cm Minimum 20cm Minimum 20cm Minimum 20cm Minimum 20cm...
Страница 26: ......
Страница 28: ...1h 24h 1h 24h 1 5 5 AUTO 5 5 5 5 50...
Страница 29: ...1...
Страница 30: ...2 9 60 10...
Страница 31: ......
Страница 32: ...5 32...
Страница 33: ...2002 96 FL E2 P1...
Страница 34: ...Manual de utilizare DEZUMIDIFICATOR R 91110...
Страница 99: ...4 52...
Страница 105: ...R290 24 0 236 ohm 0 236 ohm 100 m3 h...
Страница 106: ...R 290 R290 52 R 290 4 2 R290 1 2 3 4 5...
Страница 107: ...6 7 8 9 10...
Страница 108: ...11 Ankh 12 13 14 25 OFN 15...
Страница 109: ...16 17 80 18...
Страница 110: ......
Страница 111: ...24 0 236ohm 100 m3 h...
Страница 112: ...R290 R290 52 R290 4 R290 1 2 3 4 5 A C 2 6 7...
Страница 113: ...8 9 10 11...
Страница 114: ...12 13 14 15...
Страница 115: ...16 a b c d e f g h 80 i j k 17 18...