background image

PS10-BRD v3.2 EN Rev.A.doc 

 

2008-04-08 

  

Power Supply Module 13.8V/1.2A 

Type PS10-BRD 

v3.2 

P

RODUCT 

D

ESCRIPTION 

 

The PS10-BRD module is a spare part for PS10 power supply however it can be also used 

as autonomic power supply module. If used autonomously PS10-BRD requires 18-22VAC 
and 40W of power and may deliver up to 2A DC current without any time limit. PS10-

BRD utilizes DC/DC switched mode electronic circuit which offers high efficiency and 
small size. Also, it employs internal current limiting and short circuit protection which 

make it essentially indestructible. The reserve battery is connected to output terminals 
trough an ultra low-resistance MOS transistor, such a circuit architecture enables 

optimum performance during AC failure and during dynamic changes of load when 
excessive current consumption is required. PS10-BRD charges battery with constant 
current-constant voltage
 method, this method of charging guaranties relatively quick and 

safe charging process. The initial charging current is factory set to ~300mA, installer 
should be aware that with battery connected to PS10-BRD the total output current will be 

reduced to 1.7A. Depending on battery charging phase the output voltage of PS10-BRD 
may vary from approx. 11.5 up to 13.8V level. When battery voltage drops below ~10.0V 

level internal circuit disconnect it from load, battery is automatically reconnected when 
AC supply returns. Battery cut off circuit protect battery from deep discharge whereas 

the equipment connected to power supply from operation below 10.0V level which in 
many cases can lead to undefined system behavior. Battery is protected with 5A fuse 
which reduce maximum output current sourced from battery and protects electronic 

circuit against battery reverse connection. PS10-BRD offers two output ports (Z1 and Z2 
terminals). The nominal output voltage is factory set to 13.8V and should not be changed 

by user. PS10-BRD is equipped with two LEDs, the first one (red) indicates that module 
has AC supply while the second one (green) indicates DC output voltage.  

PSAM-1

 

A

LARM 

M

ODULE 

 

If required PS10-BRD can be equipped with optional PSAM-1 alarm module. The main 

purpose of PSAM-1 module is to detect and indicate an alarm situation of power supply to 
the external device or system. The PSAM-1 may operate in autonomic or networked 
mode and can indicate following conditions: 

 

low battery 

battery failure 

AC supply lost 

DC output overload (this state is indicated in networked mode only) 

DC output level (this state is indicated in networked mode only) 

 
In autonomic mode alarm states are indicated on three transistor outputs: ACL, LB and 
BF and on internal buzzer.  These outputs can be connected to external control panel, 

access controller or another control device which will warn authorized personnel. 
Normally, all outputs are in high resistance state, when triggered they switch to supply 

minus. The maximum current which can be sink by these output is internally limited to 
20mA while the maximum applied voltage should not exceed 15V.  

The ACL (Alternative Current Lost) output switches to active state when there is a lack of 
AC supply and it lasts for more then 4 minutes. Output returns to normal state 

immediately after AC supply returns. The LB (Low Battery) output is triggered when 
battery level drops below ~12.0V, it return whenever battery level rise above 12V. The 
BF (Battery Failure) output is triggered in case of any situation listed below: 

 

Battery fuse is off 