PRT22_EN.doc
www.roger.pl
04-04-17
PRT22
V
3.0
O
UTDOOR
P
ROXIMITY
R
EADER
General Description
The PRT22 reader is dedicated for use with access controllers which accept one of following communication standards:
!
Wiegand26 bit
!
Wiegand34 bit
!
Wiegand42 bit
!
Magstripe (ABA track 2 emulation)
!
RACS Clock&Data
The
RACS
standard is dedicated for operation with PR series controllers manufactured by Roger (
www.roger.pl
). PRT22 reader
accepts UNIQUE (EM4001/2) standard cards or compatible and is equipped with three LEDs and buzzer. Optionally it may operate
with external keypad which makes reader as Prox and PIN type. PRT22 offers
In Circuit Programming
feature which enables firmware
downloading into microprocessor memory. Reader has fully potted electronic circuit which makes adequate protection when installed
in outdoor locations.
Custom Firmware
On special request
Roger
offer custom specified versions of firmware which can be download to reader during manufacturing process
or later. For example customer may request reader that will accept only specified card numbers or equipped with other communication
standards. The firmware downloading requires special programming cable and software but doesn’t require reader de-installation.
Wiegand and Magstripe formats
When device is set to
Wiegand
or
Magstripe
format an
On/Off
led is set to green color permanently, every time a card is read or PIN
code is entered a
SYSTEM
led and buzzer are activated together for a short time. Led
Open
in normally off, applying supply minus to
[IN1] input activates
Open
led and buzzer simultaneously. PRT22 accept PIN codes followed with [#] mark, PIN codes are transmitted
immediately after [#] mark is pressed, reader sends all pressed digits, if number of digit is less then required by relevant format,
leading zeros are appended to transmitted PIN code.
RACS format
When device is set to
RACS
format all LEDs and buzzer are normally handled by access controller but there are two exceptions from
this rule:
!
when reader lost communication with controller, all three LEDs simultaneously blinks,
!
when controller is busy (e.g. during controller’s manual programming) all LEDs are off
When [IN1] is shorted with supply minus reader operation will be suspended (cards and PINs will be ignored).
Note: The
RACS
standard accepts up to 8 devices connected to controller through Clock & Data lines, due to this feature every reader
should have its individual address (ID number) which will distinguish it on Clock&Data bus. The reader ID number can be set on
programming jumpers (see jumper settings table).
TAMPER circuit
Reader is equipped with an optical TAMPER detection circuit which consists of reflecting transoptor and transistor output. When
reader case is closed the infrared beam reflects from bottom part of reader case, in this case TAMPER output line is shorted to GND.
When the bottom part of case is slightly detached from upper part the infrared beam is discontinued, TAMPER line turn into high
resistance state.
Note: The voltage applied to TAMPER output may not exceed 18V level, the maximum current which the output can sink is 20mA.
Installation
The reader should be mounted using two mounting screws, all electrical connections must be made with power supply switched off.
The selection of communication standard and other reader option can be made on jumpers.
Notes:
!
Avoid installing reader on metal surfaces, this can significantly reduce reading range.
!
When installing reader on metal surface use optional non-metal spacer (10mm thick or more) between reader and metal
surface.
!
When reader is supplied from another power source then controller, both supply minus (reader’s and controller’s) must
be connected together.
!
It is recommend to ground power supply minus.
!
Reader should not cause interferences to other equipment, however other devices can interfere with reader, avoid
installing reader close (<0.5m) to another reader or computer monitor, when an essential reading range reduction is
observed try to relocate unit.
!
PRT22 can be mounted in external location, it has full protection against outdoor condition.
Originally PRT22 is delivered without optional external keypad. When PIN identification is required installer may connect
external keypad to relevant connector available on PRT22 (see installation and wiring diagram). It is recommended to make
connection between external keypad and reader’s connector through soldering and separate individual wires with additional
insulation sleeve.
Ordering information
PRT22
PRT22 access terminal.
Technical Specification
Operating voltage range
10...16VDC (recommended linear type power supply unit)
Current consumption:
avg. 60mA
Tamper
Optical tamper circuit, open transistor output, max. sink current 20mA.
Reading range
up to 12 cm for ISO card (depends on card quality)
Card type
UNIQUE 125 KHz, ASK Modulation, 64 bit) or other types EM4001/2 compatible
Operating temp. range
-20..+60º C.
Cable distance to controller
150 meters (500 ft)
Operating humidity
0 to 95% (non condensing)
Ingress protection code:
IP30 (for internal use only, without water protection)
Dimensions
105 X 105 X 31 mm
Weight
160g
Cable assignment
Function Color
Description
+12 PINK
Supply
plus
GND BROWN
Supply
minus
CLK
GREEN
[Data 0] for Wiegand formats or [Clock] for Magstripe and RACS formats
DTA
WHITE
[Data 1] for Wiegand formats or [Data] for Magstripe and RACS formats
IN1 YELLOW
For
Wiegand
and
Magstripe
formats this input is used to activate led
OPEN
and buzzer
together, for
RACS
format this input can be used to deactivate reader and keypad
operation. In both cases input is triggered by supply minus.
TAMP GREY
Tamper
output.