background image

 

 

2/2 

 

A

PPENDIX

 

 

Fig. 3 Enclosure opening 

 

Fig. 4 Service contacts 

Table 1. Screw terminals 

Name 

Description 

12V 

Supply plus 

GND 

Ground 

RS485 bus, line A 

RS485 bus, line B 

IN1 

IN1 input line 

IN2 

IN2 input line 

IN3 

IN3 input line 

IO1 

IO1 output line 

IO2 

IO2 output line 

NC 

REL1 relay output (NC) 

COM 

REL1 relay common terminal 

NO 

REL1 relay output (NO) 

 

Table 2. Specification 

Supply voltage 

Nominal 12VDC, min./max. range 10-15VDC 

Current 

consumption 

(average) 

~60 mA 

Inputs 

Three  parametric  inputs  (IN1..IN3)  internally 
connected  to  the  power  supply  plus  through  a 
5.6

kΩ  resistor.  Approx.  3.5V  triggering  level  for 

NO and NC inputs. 

Relay output 

Relay  output  (REL1)  with  single  NO/NC  contact, 
30V/1.5A DC/AC max. load 

Transistor outputs 

Two  (IO1,  IO2) open collector outputs, 15VDC/1A 
max. load 

Tamper protection 

Enclosure opening reported to access controller 

Proximity cards 

13.56MHz  MIFARE  Ultralight,  Classic,  DESFire 
EV1 and Plus 

Reading range 

Up to 7 cm for MIFARE Ultralight, Classic 
Up to 4 cm for MIFARE DESFire EV1, Plus 

Distance 

1200m  maximal  cable  length  for  RS485  bus 
between controller and terminal 

IP Code 

IP41 

Environmental 

class 

(according to EN 50133-1) 

Class  II,  indoor  general  conditions,  temperature:  -
10°C  to  +50°C,  relative  humidity:  10  to  95%  (no 
condensation) 

Dimensions H x W x D 

155 x 85 x 22 mm 

Weight 

~180g 

Certificates 

CE 

 

 

Fig. 5 Connection of terminals and expanders to MC16 access controller 

 

Fig. 6 Typical control of 230VAC supply by terminal with card holder 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

This  symbol  placed  on  a  product  or  packaging  indicates  that  the 
product  should  not  be  disposed  of  with  other  wastes  as  this  may 
have a negative impact on the environment and health. The user is 
obliged  to  deliver  equipment  to  the  designated  collection  points  of 
electric and electronic waste. For detailed information on recycling, 
contact  your  local  authorities,  waste  disposal  company  or  point  of 
purchase.  Separate  collection  and  recycling  of  this  type  of  waste 
contributes to the protection of the natural resources and is safe to 
health and the environment. Weight of the equipment is specified in 
the document. 

 

Contact: 

Roger Sp. z o. o. sp. k. 

82-400 Sztum 

Gościszewo 59 

Tel.: +48 55 272 0132 
Fax: +48 55 272 0133 

Tech. support: +48 55 267 0126 

E-mail

[email protected]

 

Web

www.roger.pl

 

 

Отзывы: