Fig. 7 Device select window in RogerVDM software
Fig. 8 Configuration window in RogerVDM software
Table 3. Configuration parameters
Parameter
Values
Description
General
Device Name
16 ASCII
characters
Device description which can be filled with any comment by
installer
Transmission Format
RACS CLK/DTA
Address
0..15
Device address on RACS CLK/DTA bus. Default address
ID=0 is required for communication with HRC controller.
Communication
timeout
0..255
The device signals communication failure when selected
timeout [0.5s] elapses. When 0 is selected then failure is
not signalled at all.
Acoustic Signalization
Buzzer loudness
level
0..100%
Buzzer loudness level. Buzzer is switched off when 0 level is
selected
CSN Number Settings