background image

ROGER s.c.  

 

   DIAL 1602 v1.0 25/11/1999

 

 

 
 

4

 - 

(if it is allowed) or direct to the ready mode. See the schematic of 
changing the dialer modes. 
 

BLOCKING MODE

BLOCKING MODE

BLOCKING MODE

BLOCKING MODE

 

 
The blocking mode, if allowed in the configuration procedure, 
enables a use of the dialer as a double line alarm panel. In the 
blocking mode the dialer ignores the alarm condition in the lines A 
and B. However, if such a condition occurs, the dialer displays the 
name of the line in which the alarm was initiated. You switch to the 
blocking mode (if it is allowed) from the alarm mode, pause mode 
or ready mode by entering the user code or by going to the 
programming mode (see the schematic of changing the dialer 
modes).  
 

READY MODE

READY MODE

READY MODE

READY MODE

 

 
In this mode the program monitors the alarm inputs. When an 
alarm is recognized in an alarm line, the system starts counting of 
the time delay for the specific line and then it goes to the alarm 
mode. Each time the ready mode is activated, which is performed 
after entering the user code, it is preceded by performing the 
system testing procedure and counting the output delay. When the 
blocking line C is released in the ready mode, the alarm inputs A 
and B are blocked. The lines A and B remain blocked as long as 
the line C remains released. The release condition of the blocking 
line C is signalized by displaying the letter C on the dialer display.  
 

ALARM MODE

ALARM MODE

ALARM MODE

ALARM MODE

 

 
Single message dialer. 

After recognition of the alarm condition in the line A (B), the dialer 
begins counting the A (B) input delay. If you do not enter the 
correct user or installer code during the counting of the input delay, 
the dialer will start dialing the numbers in the list L1..L10, in the 
sequence the numbers were put in the list. After making the 
connection, the dialer transmits the alarm tone and announcement 
five times, then it goes to the next number. The described action is 
repeated twice. During the alarm action any signals in the alarm 
inputs A and B are ignored. 

 
Double message dialer 

In this case the alarm mode initialization algorithm is identical as 
for the single message dialer. The difference is that if an alarm 
was activated in the input A, the system dials the numbers from 
the list A1..A5 and the announcement A is transmitted. If an alarm 
was activated in the line B, the system dials the numbers from the 
list B1..B5 and the announcement B is transmitted. During the 
alarm action the dialer displays two letters informing about the type 
of the current alarm action and the name of the alarm input, which 
initiated the alarm, to the right from the caption Ready.  
 
 
Alarm types: 
AG – loud alarm            

(activates the PGM output) 

AC – silent alarm             

(does not activate the PGM output) 

AN – duress alarm     

(silent alarm in the line A)  

 

DURESS ALARM

DURESS ALARM

DURESS ALARM

DURESS ALARM

 

 
You can initiate the duress alarm in the Blocking or Ready mode 
by entering the duress code: 
[*] digit [*]  
Regardless the line A programming as silent or loud, or the dialer 
configuration as single message or double message, the duress 
alarm is performed silently and corresponds the alarm initialization 
in the line A. Following the completion of the duress alarm, the 
dialer goes direct to the Ready mode. 
 

PAUSE MODE

PAUSE MODE

PAUSE MODE

PAUSE MODE

 

 
Single message dialer 

When the notification procedure is completed, the dialer switches 
to the pause during which it blocks both alarm inputs. After the 
pause time has elapsed, the system returns to the ready mode and 
stops blocking both alarm inputs.  
 

Double message dialer 

When the notification procedure is completed, the dialer switches 
to the pause during which it blocks the alarm input from which the 
alarm was initiated, monitors the other alarm input and is ready to 
start the alarm action from the line, provided it is initiated. During 
the notification action both alarm inputs are blocked. After the 
pause time has elapsed, the system returns to the ready mode and 
stops blocking both alarm inputs.  
 

TELEPHONE LINE LISTENING

TELEPHONE LINE LISTENING

TELEPHONE LINE LISTENING

TELEPHONE LINE LISTENING    

 
Using the headphone output, in addition to listening to the alarm 
announcement, you can listen to the notifications, since the 
telephone line tones are retransmitted to the headphone output. 
 

EXTERNAL CALL ANSWERING FUNCTION

EXTERNAL CALL ANSWERING FUNCTION

EXTERNAL CALL ANSWERING FUNCTION

EXTERNAL CALL ANSWERING FUNCTION

 

 
The function allows you to obtain remote information if there was 
an alarm activated at the facility where the dialer is installed. You 
can get such information by dialing the dialer telephone number. In 
this function the dialer, being in the ready mode, after recognition 
of 8 call tones, connects into the telephone line and transmits an 
acoustic signal for 20s. If no alarm occurred at the facility from the 
time the dialer went to the ready mode, the transmitted acoustic 
signal is a two-second acoustic tone, repeated cyclically. If there 
was an alarm at the facility, which was not reset, the dialer 
transmits a signal, which is modulated in the identical way as the 
signal preceding the alarm announcement. 
 

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION

 

 
Power supply           

11V..15V  

Input current in ready mode 

typically  45mA  

Dimensions     L x W x H    

215 X 95 X 27 

Temperature range 

0..50 C˚ 

 

DRAWINGS

DRAWINGS

DRAWINGS

DRAWINGS    

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание DIAL 1602M

Страница 1: ...AUTOMATIC TELEPHONE ALARM DIALER DIAL 1602M OPERATION AND INSTALLATION INSTRUCTION MANUAL ...

Страница 2: ...aler is originally equipped with a 3V 120mAh battery which guarantees keeping up the memory for minimum 60 days in case of a power supply loss The memory stores the alarm telephone numbers alarm messages history of events and dialer configuration parameters A power supply loss results only in resetting the time and date A lack or low battery voltage lower than 2 7V at a power supply loss results i...

Страница 3: ...the power supply voltage is higher than 9 5V the dialer will display the Roger DIAL1602 message and test the RAM memory If the dialer programming has been lost the First start of dialer message is displayed and then DIALER PROGRAMMING LOST ENTER DEFAULT CODE Then you should press the key and after message Enter code is displayed you should enter the default installer code i e 1234 end the code ent...

Страница 4: ...e duration of PGM output activation from the moment a loud alarm is switched on min 000s max 255s Pause between alarms 000min In case of a double message dialer it specifies the duration of alarm line blocking from the moment the notification action was stopped which was initiated in this line It is shared by both alarm inputs In case of a single message dialer both alarm lines are blocked for the...

Страница 5: ... the alarm to the right from the caption Ready Alarm types AG loud alarm activates the PGM output AC silent alarm does not activate the PGM output AN duress alarm silent alarm in the line A DURESS ALARM DURESS ALARM DURESS ALARM DURESS ALARM You can initiate the duress alarm in the Blocking or Ready mode by entering the duress code digit Regardless the line A programming as silent or loud or the d...

Страница 6: ...ROGER s c DIAL 1602 v1 0 25 11 1999 5 ...

Страница 7: ...ROGER s c DIAL 1602 v1 0 25 11 1999 6 Schematic of changing the DIAL1602 dialer operating modes NOTE Pause after the duress alarm equals 0 minutes INSTAL CODE Installer code USR CODE User Code ...

Отзывы: