B.  The  control  comes  preset  with  the  “empty  bowl 

timer”  (or  parts  jam  timer)  disabled.    Once 

enabled,  the  bowl  will  stop  feeding  when  parts 

have not passed the sensor for the set time. The 

empty bowl timer can be adjusted from 5 to 255 

seconds  under  the  “timer  settings”  menu.  Press 

the “1/0” key or toggle the parts sensor to restart 

the control.  The auxiliary output can be set up to 

turn on a signaling device.  See the section that 

describes the auxiliary output for more details. 

 

20.  Auxiliary Output Settings

 

The “Aux Output Mode” menu contains the menu that 

controls the auxiliary output (Aux Out) operation.  

A.  The  factory-default  “Normal”  setting  allows  the 

auxiliary output to turn on and off with the output 

of the feeder.   

B. The auxiliary output can be set to have its signal 

inverted  from  the  output  of  the  feeder.    Set  the 

“Aux Out” parameter to “Invert” to activate it.   

C. The auxiliary output can be set so that the alarm 

signal can indicate when the “Empty Bowl” timer 

has  timed  out.  Set  the  “Aux  Out”  parameter  to 

“Alarm” to activate it. 

D. The auxiliary output can be set so that the alarm 

signal  can  be  inverted  when  the  “Empty  Bowl” 

timer has timed out. Set the “Aux Out” parameter 

to “Inv Al” to activate it. 

E.  The  auxiliary  output  can  be  set  so  that  an  air 

solenoid can be activated 1 second before feeding 

begins and continue for 4 seconds after feeding 

ends.  This feature is helpful for parts orientation.  

Set the “Aux Out” parameter to “Air Jet” to activate 

this feature. 

21.  Diagnostics

 

A.  The  first  menu  item  under  the  diagnostic  menu 

shows the control type and feeder’s load current.   

B. The next five items show certain software registers 

and the software versions which may be helpful to 
Rodix staff while troubleshooting over the phone.  

22.  Security Settings

 

The “Security” menu contains the portion of the menu 

that controls access to the program menu settings.  

When enabled, the security code is a number from 

000  to  999.    The  preset  code  is  123.    It  may  be 

changed. 

A.  The  control  comes  with  the  security  setting 

“Unlocked”  so  the  control  can  be  set  up.    The 

amplitude  can  be  adjusted  from  the  normal 

operating display.  Press and hold “Enter” to enter 

the  program  menu  and  adjust  the  software 

settings. 

B.  The  amplitude  only  (Ampl.  Only)  adjustment 

allows operators to adjust the amplitude through 

the  normal  operating  display,  but  not  get  to  the 

program menu settings without the security code.   

C.  The  “Lock”  setting  locks  the  control  from  any 

adjustment without the use of the security code.   
If the security code has been forgotten, enter the 
security code #010, 

press and hold

 “Enter” until 

entry has been granted.  Note: ignore the “Wrong 
Security  Code”  message.    Once  in  the 
programming  menu  be  sure  to  set  the  security 
code. 

23.  Default Memory

 

Occasionally it is nice to get back to a known setting. 
Once  a  feed system has  been set  up  properly,  the 
setting  should  be  manually  saved  into  the  “Save 
Settings1”  memory.    If  an  operator  disturbs  the 
settings, the “Restore Settings1” feature can restore 
the control to a known good set up.  When different 
parts are used on the same feed system, two other 
memory locations called “Save Setting2” and “Save 
Settings3” can be used for other parts. Operators can 
recall settings 1, 2 or 3 based on the part being used.  
The  “Factory  Reset”  selection  will  put  the  original 
factory settings into the memory. 

24.  Language

 

The run display and programming menus can be set 
to  display  in  English,  Spanish  (Espa

ñ

ol),  French 

(Français), or German (Deutsch).  

 

 

25. CFR Set Point 

The CFR set point sets the amplitude vibration level 
that the control regulates to. The VF Series control 
adjusts  the  amplitude  automatically  to  match  the 
CFR set point. The CFR set point can be adjusted by 
the depression of the “UP” and “DOWN” arrows keys. 
Holding an arrow key down will adjust the amplitude 
setting instead of the CFR set point.  The CFR set 
point can also be controlled by a 4-20mA signal. 

 

 

The CFR set point only appears on the display when 
the “Amplitude Source” menu under power settings 
is set to “Auto Track” and the CFR sensor is attached.   

 

26. Fault Messages 

The VF control has error and warning messages 
that relate to “Over-Amps”, “Over-Temp” and Bowl 
out of parts timers.  To clear the message or fault, 
press the “1/0” button twice. “Coarse and Fine Scan 
Error” mean not enough vibration was measured 

during an Autoscan. Reduce Resonate Threshold. 

 

 

WARNING: 

Fuses should be replaced with Littelfuse 3AB 

"Fast Acting" type or equivalent of 

manufacturer's original value. 

Mounting this control on a vibrating surface will 
void the warranty. 

 

 

Warranty 

Rodix Control Products are Warranted to be free from 
defects in material and workmanship under normal use 
for a period of two years from date of shipment.  

For 

the  full  description  of  the  warranty,  terms,  and  software 
license, please contact the factory. 

 

For  assistance  installing  or  operating  your  Rodix  Feeder 
Cube®  please  call  the  factory  or  visit  our  web  site. 
Technical help is available to answer your questions and 
email any needed information.  To return a control for IN or 
OUT of warranty service, please ship it prepaid to: 

Rodix Inc.,  ATTN: Repair Department 

If under warranty, Rodix will repair or replace your control 
at no charge; If out of warranty, we will repair it and you will 
be billed for the repair charges (Time and Material) plus the 
return  freight.    Quotes  for  repairs  are  available  upon 
request.  A brief note describing the symptoms helps our 
technicians address the issue. 

 

Feeder Cube® and Auto Tune® are registered TM of Rodix Inc. 
Banner

 is a registered Trademark of Banner Engineering Corp, 

9714 10th Ave, Minneapolis, MN 55441 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

RODIX, INC.

 

2316 23

rd

 Avenue, Rockford, IL 61104 

Toll Free (800) 562-1868

 

E-mail  [email protected] 

www.rodix.com 

1 VF Set Up V2_01.docx 8/19/20  Page 7 

Содержание 121-200-0769

Страница 1: ...ent Unit C 3 Amps at 120V or 2 Amps at 240V Model Information for each unit The Autotune Series of Variable Frequency Feeder Cubes generates an output frequency for feeding that is independent from th...

Страница 2: ...RODIX INC Toll Free 800 562 1868 FAX 815 316 4701 Email custserve rodix com rodix com VF 393 H cover docx 10 3 20 Page 2 RODIX INC FEEDER CUBE VF Series Wiring Diagram Figure 1...

Страница 3: ...ngs 2 Enter Restores User Settings 2 Restore Settings 3 Enter Restores User Settings 3 Save Settings 1 Enter Saves User Settings 1 Save Settings 2 Enter Saves User Settings 2 Save Settings 3 Enter Sav...

Страница 4: ...single phase 120 or 240 VAC installations to bypass the phase 2 fuse L2 To bypass remove the wire connecting TB1 L2 to the L2 fuse holder Remove the terminal end of the wire connecting the L2 fuse to...

Страница 5: ...r setting is displayed in the following manner A 50 0 8 Limiting the Maximum Output of Control The Max Amplitude setting can be adjusted to keep a vibratory feeder from hammering or vibrating excessiv...

Страница 6: ...arts load fluctuations adjust the frequency down by 2 or 3Hz so that the feeder becomes slightly over tuned B Auto Scan scans to locate the bowl s resonate frequency Once auto tracking has found the r...

Страница 7: ...to a known setting Once a feed system has been set up properly the setting should be manually saved into the Save Settings1 memory If an operator disturbs the settings the Restore Settings1 feature ca...

Страница 8: ...ies Control 1 Add a wire from term TB2 1 of the VF master control to TB2 11 of the subordinate control 2 Add a wire from TB2 2 of the VF master control to TB2 12 of the subordinate control 3 Move the...

Страница 9: ...f a nearby noise source Solutions for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock inpu...