Rodix 121-200-0763 Скачать руководство пользователя страница 10

 
 
 
 
 
 

 

RODIX SOLUTION 

 

Good wiring practices for 

avoiding electrical noise 

problems. 

 

Rodix controls have been designed with a 
high degree of immunity to electrical 
noise; however, depending on the control 
installation, electrical noise can cause 
problems.  These problems occur in less 
than 1% of the product installations.  Most 
electrical noise problems can be avoided 
by following some simple guidelines.  
Good wiring practices need to be used to 
prevent electrical noise from interfering 
with your control’s operation.  Another 
name for electrical noise is Electro-
Magnetic Interference (EMI). 

 

Symptoms of Electrical Noise 

The symptoms of electrical noise would 
appear as follows: a brief pause or a brief 
“bump” in the vibratory feeder’s output 
that the control automatically recovers 
from.  In rare cases the control will either 
stop operating or run continuously at full 
power in 120 pulse mode until the power 
switch is slowly cycled OFF and ON.   

 

Sources of Electrical Noise 

Electrical noise is generated by devices 
like relay coils, solenoid valves, 
contactors, servo motors, and variable 

frequency inverter drives.  The electrical 
noise is then transferred to another device 
by one of three ways.  The noise could be 
conducted through the power wires, or 
capacitively coupled from wire to adjacent 
wire, or it is transmitted from the wires of 
a nearby noise source. 

 

Solutions for Electrical Noise 

1.  Use shielded wires for all I/O (Input / 
Output) signals.  The I/O signals may 
include: 4-20mA input, Run input, Sensor 
input, 0-5VDC input, Interlock input or 
AUX output.  The shield “drain” wire 
should be tied to the chassis in the Rodix 
control.  The drain wire should be kept 
shorter than 2”.  Please see the enclosed 
picture.

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Example of a “drain” wire termination 

 

2.  Never run I/O signal wires in the same 
conduit or raceway as AC power lines 
such as wires to motors, solenoids, 
heaters, welders and Rodix controls, etc. 

 

3.  I/O wires within an enclosure should 
be routed as far away as possible from 
relays, solenoids, transformers, power 
wiring and other noisy equipment.  Keep 
the I/O signal wires separate from the 
control’s input and output power wiring.  
Secure the wires in place.   

 

4.  Whenever relays or solenoid valves 
are used, install a Snubber on them to 
reduce electrical noise.  Use a diode on a 
DC coil.  Use a RC Snubber on an AC 
coil. 

 

 
 
 
 
 
 
 
 
 

 

5.  In extremely high EMI environments, 
Power Line Filters and ferrite beads can 
be effective.  Install ferrite beads on I/O 
signal wires as close as possible to the 
circuit board terminal strip.  Loop the wire 
through the bead several times or use 
several beads on each wire for additional 
protection. 

 
 
 

RODIX, INC.

 

Toll Free (800) 562-1868

 

E-mail [email protected] 

www.rodix.com 

 

2000,2014 RODIX INC. Good Wiring 1/31/2014 

RODIX INC. 

FEEDER CUBE

 

RODIX SOLUTION .408 

Drain 
Wire

RELAY
COIL

SNUBBER

VAC

104M06QC47

QUENCH-ARC

RECTIFIER
DIODE

RELAY
COIL

1N4006

VDC

+

-

Содержание 121-200-0763

Страница 1: ...at 240V Model Information for each unit The Autotune Series of Variable Frequency Feeder Cubes generates an output frequency for feeding that is independent from the power line frequency An optional vibration sensor P N 123 215 can be used to maintain the vibratory feeder at a constant feed rate The start stop operation of the output can be controlled with an optional parts sensor For more informa...

Страница 2: ...RODIX INC Toll Free 800 562 1868 FAX 815 316 4701 Email custserve rodix com rodix com VF 3 2 H cover docx 10 3 2020 Page 2 RODIX INC FEEDER CUBE VF Series WIRING DIAGRAM Figure 1 ...

Страница 3: ...ings 2 Enter Restores User Settings 2 Restore Settings 3 Enter Restores User Settings 3 Save Settings 1 Enter Saves User Settings 1 Save Settings 2 Enter Saves User Settings 2 Save Settings 3 Enter Saves User Settings 3 Factory Reset Enter Resets Control to Factory Default Settings Shown in bold Normal Display Message Priority The normal operating display shows the status of the control with regar...

Страница 4: ...AC installations to bypass the phase 2 fuse L2 To bypass remove the wire connecting TB1 L2 to the L2 fuse holder Remove the terminal end of the wire connecting the L2 fuse to the power switch and connect it to TB1 L2 1 Parts Sensor Input Photo sensor or Proximity Switch Connect a current sourcing PNP sensor to TB2 as shown on the enclosed wiring diagram The sensor must be able to operate on 24VDC ...

Страница 5: ...er setting is displayed in the following manner A 50 0 8 Limiting the Maximum Output of Control The Max Amplitude setting can be adjusted to keep a vibratory feeder from hammering or vibrating excessively when the control is turned up to full power The maximum power setting can be found under the Power menu It can be adjusted from 100 0 down to 40 0 Caution it is recommended when using the CFR fea...

Страница 6: ...adjust the frequency down by 2 or 3Hz so that the feeder becomes slightly over tuned B Auto Scan scans to locate the bowl s resonate frequency Once auto tracking has found the resonate frequency it can maintain the resonate frequency and amplitude of the feeder as the parts load changes The CFR sensor is needed in order for auto tracking to operate and Auto Tracking needs to be turned on under bot...

Страница 7: ...known setting Once a feed system has been set up properly the setting should be manually saved into the Save Settings1 memory If an operator disturbs the settings the Restore Settings1 feature can restore the control to a known good set up When different parts are used on the same feed system two other memory locations called Save Setting2 and Save Settings3 can be used for other parts Operators c...

Страница 8: ...ries Control 1 Add a wire from term TB2 1 of the VF master control to TB2 11 of the subordinate control 2 Add a wire from TB2 2 of the VF master control to TB2 12 of the subordinate control 3 Move the run jumper on the subordinate control from TB2 6 TB2 7 to TB2 5 TB2 6 How to Interlock an FC 200 Series to a VF Series Control 1 Remove the RUN jumper from TB2 8 9 of the subordinate control 2 Add a ...

Страница 9: ...operation Note It takes 72 hours for the adhesive to fully cure at 70 F Alternatively 8 or M4 screws can be used to mount the sensor to the feeder The mounting holes are 1 375 3 49cm apart D ROUTE THE SENSOR CABLE to protect it from strain due to vibration The cable that attaches to the sensor will not break from normal vibration however some care should be used when routing the sensor cable from ...

Страница 10: ...of a nearby noise source Solutions for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock input or AUX output The shield drain wire should be tied to the chassis in the Rodix control The drain wire should be kept shorter than 2 Please see the enclosed picture Example of a drain wire terminati...

Отзывы: