B-16
Application Notes
Start At PowerUp
A powerup delay time of up to 30 seconds can be programmed through
[Powerup Delay], parameter 167. After the time expires, the drive will start
if all of the start permissive conditions are met. Before that time, restart is
not possible.
[Powerup Delay]
Time Expired?
Start At PowerUp
Yes
Powerup Terminated!
Normal Mode
No
No
No
Powerup Start
Is the terminal block Run,
Run Forward or Run Reverse
Input Closed?
Yes
Yes
All Start Permissives Met?
1. No fault conditions present.
2. No Type 2 alarm conditions present.
3. The terminal block programmed
enable input is closed.
4. The Stop input (from all sources) is
received.