C-14
Application Notes
Example:
Calculate the maximum power of a 5 HP, 460V motor connected to a 480V rated drive
supplied with 342V Actual Line Voltage input.
•
Actual Line Voltage / Nominal Motor Voltage = 74.3%
•
74.3%
×
5 HP = 3.7 HP
•
74.3%
×
60 Hz = 44.6 Hz
At 342V Actual Line Voltage, the maximum power the 5 HP, 460V motor can produce is
3.7 HP at 44.6 Hz.
Voltage Tolerance
Drive Rating
Nominal Line
Voltage
Nominal Motor
Voltage
Drive Full Power
Range
Drive Operating
Range
200-240
200
200†
200-264
180-264
208
208
208-264
240
230
230-264
380-400
380
380†
380-528
342-528
400
400
400-528
480
460
460-528
500-600
600
575†
575-660
432-660
Drive Full Power Range =
Nominal Motor Voltage to Drive Rated V 10%.
Rated current is available across the entire Drive Full Power Range
Drive Operating Range =
Lowest† Nominal Motor Voltage - 10% to Drive Rated V 10%.
Drive Output is linearly derated when Actual Line Voltage is less than
the Nominal Motor Voltage
HP
@ Motor (Drive Output)
Actual Line Voltage (Drive Input)
Full Power Range
Drive Operating Range
Nominal Motor Voltage -10%
Nominal Motor Voltage
Derated Power Range
No Drive
Output
Drive Rated Voltage
Drive Rated V10%
5 HP
3.7 HP
HP
@ Motor (Drive Output)
Actual Line Voltage (Drive Input)
342V
460V
No Drive
Output
480V
528V