Chapter 3
Creating a Program
3–10
Monitoring Your Data File
To verify that the output and input data files for the I/O modules have been
created, you can call up data files for the I/O.
1. Press
[F1] – EDT_DAT
. The following display appears:
O0:3.0/0 = 0
Address
15 data 0
O0:3.0
0000 0000
F1
F2
F3
F4
F5
ADDRESS NEXT_FL PREV_FL NEXT_PG PREV_PG
OFL
8 bits
This is file 0, the output data file. It indicates that slot 3 of the controller has
8 bits assigned (representing outputs
O:3/0
through
O:3/7
). (For more
information, see the section concerning “Addressing External I/O” in
chapter 2.)
2. Press
[F2] – NEXT_FL
. The following display appears:
I1:1.0/0 = 0
Address
15 data 0
I1:1.0
0000
I1:2.0
0000 0000
F1
F2
F3
F4
F5
ADDRESS NEXT_FL PREV_FL NEXT_PG PREV_PG
OFL
8 bits
4 bits
This is file 1, the input data file. It indicates that slot 1 of the controller has 4
bits assigned (representing inputs
I:1/0
through
I:1/3
), and that slot 2 has 8
bits assigned (representing inputs
I:2/0
through
I:2/7
).
3. Now press
[ESC]
, then
[ENTER]
. The following display appears. You
are now ready for the next section.
File Name:
Prog Name:1000
File Name
Type Size(Instr)
0
System *
1
Reserved *
2
Ladder *
F1
F2
F3
F4
F5
OFL
CHG_NAM CRT_FIL EDT_FIL DEL_FIL MEM_MAP
>
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Allen-Bradley 1747-PT1
Страница 58: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 72: ...Glossary G 4 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 76: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 77: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...