Rockwell Automation SMC FLEX Скачать руководство пользователя страница 14

14

 SMC™ Flex  Quick Start

Troubleshooting - Abbreviated Listing

For a complete list of fault codes and troubleshooting tips, refer to the SMC Flex User Manual.

Display Fault Fault Code

Enabled

Possible Causes

Possible Solutions

Line Fault with 
Phase Indication

1, 2, 3

prestart 

only

Missing supply phase

Motor not connected properly

Incoming 3-phase voltage instability

Check for open line (i.e., blown fuse)

Check for open load lead

Verify power quality 

Shorted SCR 
with Phase 
indication

4, 5, 6

all

Shorted power module

Check for shorted SCR, replace power module if necessary

Open Gate with 
Phase Indication

7, 8, 9

start or 

stop

Open gate circuitry

Loose gate lead

Perform resistance check; replace power module if necessary

Check gate lead connections to the control module

PTC Power Pole 
and SCR 
Overtemp

10, 11

Controller ventilation blocked

Controller duty cycle exceeded

Fan failure

Ambient temperature limit exceeded

Failed thermistor

Check for proper ventilation

Check application duty cycle

Wait for motor to cool or provide external cooling

Replace power module or control module as needed
Replace fan

Motor PTC

12

running

Motor ventilation blocked

Motor duty cycle exceeded

PTC open or shorted

Check for proper ventilation

Check application duty cycle

Wait for motor to cool or provide external cooling

Check resistance of PTC

Open Bypass 
with phase 
indication

13, 14, 15

running

Control voltage is low

Inoperable power module bypass

Check control voltage power supply

Replace power module

Check control module TB2…TB4 and TB5…TB7 for securness

Check Aux 1, 2, 3, 4 configurations are not set to External 
Bypass

No Load Fault

16, 17, 18, 40

prestart 

only

Loss of load side power wiring

Start command cycled unexpectedly with motor rotating

Check all load side power connections

Check motor windings

Line Unbalance

19

running

Supply unbalance is greater than the user-programmed value

The delay time is too short for the application

Check power system and correct if necessary

Extend the delay time to match the application requirements

Overvoltage

20

running

Supply voltage is greater than user programmed value

The delay time is too short for the application

Check power system and correct if necessary

Correct the user-programmed value

Extend the delay time to match the application requirements

Undervoltage

21

running

Supply voltage is less than user programmed value

The delay time is too short for the application

Check power system and correct if necessary

Correct the user-programmed value

Extend the delay time to match the application requirements

Overload

22

running

Motor overloaded

Overload parameters are not matched to the motor

Check motor overload condition

Check values for overload class and motor FLC

Verify current draw of the motor

Underload

23

running

Broken motor shaft, belts, toolbits, etc..

Pump cavitation

Incorrect user setting

Check pump system, machine drive components, and loading

Check settings

Repair or replace motor

Jam

24

running

Motor current has exceeded the user programmed jam level

Correct source of jam or excessive loading

Check programmed time value

Stall

25

running

Motor did not reach full speed by the end of the programmed 
ramp time

Incorrect user setting

Correct source of stall or excessive loading

Adjust SMC starting parameters to compensate for load

Phase Reversal 

26

prestart 

only

Incoming supply voltage is not in the expected ABC sequence

Check power wiring, correct if necessary

Network and 
Comm's Loss

30, 31, 32
27, 28, 29

all

DPI network loss

Communication disconnection at the serial port

Check communication adapters and verify connection to SMC

Reconnect each DPI connected device

Ground Fault

33

running

Ground fault current level has exceeded programmed value

The delay time is too short for the application

Check power system and motor; correct if necessary

Check programmed ground fault levels to match application 
requirements

Extend the delay time to match the application requirements

Power Loss with 
phase indication

35, 36, 37

start or 

stop

Missing supply phase (as indicated)
Internal CT problem

Check for open line (i.e., blown line fuse)
Replace power pole as indicated

Line Loss with 
phase indication

41, 42, 43

start or 

stop

Incoming 3-phase voltage instability or distortion

High impedance connection

Check supply voltage for capability to start/stop motor

Check for loose connections on line side or motor side of 
power wires

Verify and correct input power quality

Internal 24V and 
System Faults

44, 45, 46, 

128…209

all

Low line condition

Excessive load on 

Check the control power, verify it is within the specification

Check connections and grounding to the SMC control 
terminals

Replace control module

Содержание SMC FLEX

Страница 1: ...precautions For safety of maintenance personnel as well as others who might be exposed to electrical hazards associated with maintenance activities follow all local safety related work practices for example the NFPA 70E Part II in the United States Maintenance personnel must be trained in the safety practices procedures and requirements that pertain to their respective job assignments For detailed...

Страница 2: ...shooting testing etc must be performed by properly qualified personnel using appropriate local safety work practices and precautionary measures Failure of solid state power switching components can cause overheating due to a single phase condition in the motor To prevent injury or equipment damage the use of an isolation contactor or shunt trip type circuit breaker on the line side of the SMC is r...

Страница 3: ...t The maximum output current through the DPI port is 280 mA When installing or inspecting protective modules make sure that the controller has been disconnected from the power source The protective module should be inspected periodically for damage or discoloration Replace if necessary An incorrectly applied or installed controller can damage components or reduce product life Wiring or application...

Страница 4: ...closure Ratings Standard Device Rating IP00 NEMA Open Type Minimum Required Enclosure IP23 NEMA Type 1 Recommended Enclosure IP54 NEMA Type 12 sizing guide in User Manual Enclosure Internal Temperature 5 50 C 23 122 F Orientation and Clearance Mounting Orientation Vertical Minimum horizontal clearance 0 cm 0 in Minimum vertical clearance 15 cm 6 in Lifting Points ...

Страница 5: ... 0 5 90 203 0 8 00 5 7 kg 12 5 lb 108 135 443 7 17 47 196 4 7 74 212 2 8 35 15 0 kg 33 0 lb 201 251 560 0 22 05 225 0 8 86 253 8 9 99 30 4 kg 67 0 lb 317 480 600 0 23 62 290 0 11 42 276 5 10 89 45 8 kg 101 lb 625 780 1041 1 41 00 596 9 23 50 346 2 13 63 179 kg 395 lb 970 1250 1041 1 41 00 596 9 23 50 346 2 13 63 224 kg 495 lb 23 24 25 26 27 28 29 30 31 32 33 34 11 12 13 14 15 16 17 18 19 20 21 22 ...

Страница 6: ... 120 240 mm2 4 0 500 MCM 1 1 Terminal Description Terminal Description Footnotes 11 Control Power Input 23 PTC Input Do not connect any additional loads to these terminals These parasitic loads may cause incorrect operation When set for External Bypass mode the SMC Flex can be used to control a properly sized externalcontactorandoverloadoncethemotor reaches full speed The SMC Flex overload functio...

Страница 7: ...Number of Wires per Terminal 2 AC Control Voltage Input 100 240V AC or 24V AC 10 15 Supply Type 1 phase 50 60 Hz 24V AC Power Requirement 130VA 100 240V AC Power Requirement 75VA DC Control Voltage Input 24V DC 10 15 Inrush Current 5 A Inrush Time 250 ms Transient Watts 60 W Transient Time 500 ms Staedy State Watts 24 W Recommended Supply 1606 XLP50E Fan Power Input AC only separately wired F5 F13...

Страница 8: ...4 3 6 5 L1 L2 L3 M 3 2 U K1 2 1 1 4 V 4 3 3 6 W 6 5 5 M 3 L1 2 K1 1 2 1 L2 4 3 4 3 L3 6 2 1 4 3 6 5 5 6 5 U1 V1 W1 W2 U2 V2 Diagrams per IEC Symbology L1 L2 L3 T1 T2 T3 Motor T6 T4 T5 Delta Connection with Shorted SCR Protection Optional Mode K1 Delta Connection with Isolation Contactor Optional Mode Line Connection with Isolation Contactor Default Mode Delta Connection with Shorted SCR Protection...

Страница 9: ...L N L Programming Notes Aux 4 Set for Fault Parameter 132 Set for Diable Programming Notes Aux 1 Set for Normal Aux 4 Set for Up to Speed FAN Start L1 L N L FAN K1 A1 A2 Stop Connection Required for DPI Control Fig 1 x 3 Wire Control With or Without DPI control Isolation Contactor K1 and Up to Speed Indication Fig 1 x 2 Wire Control No DPI control or Option Stopping with Fault Indication Fan Power...

Страница 10: ...tion Programming Notes Aux 1 Set for Normal Aux 4 Set fot Alarm Start L1 L N L FAN K1 A1 A2 Stop Fig 1 x 3 Wire Control with Option Stopping DPI control Isolation Contactor K1 and Alarm Indication Option Stop Programming Notes Aux 1 Set for Normal Parameter 87 Logic Mask must be set for DPI Control Value of 4 enables HIM control only Value of 32 enables Communication Port control only Value of 44 ...

Страница 11: ...C Overload Reset Overload A Lvl Parameter Mgmt Underload F Lvl Underload F Dly Underload A Lvl Underload A Dly Parameter Mgmt Undervoltage F Lvl Undervoltage F Dly Undervoltage A Lvl Undervoltage A Dly Parameter Mgmt Overvoltage F Lvl Overvoltage F Dly Overvoltage A Lvl Overvoltage A Dly Parameter Mgmt Unbalance F Lvl Unbalance F Dly Unbalance A Lvl Unbalance A Dly Parameter Mgmt Jam F Lvl Jam F D...

Страница 12: ...ter 24 Option Input 2 Allows the user to select the operation of terminal 15 Option Input 2 Disable Slow Speed Dual Ramp Fault Fault NC Network Clear Fault Disable Parameter 32 Stop Mode Allows the user to program the SMC Flex controller for the type of stopping that best fits the application Soft Stop Linear Speed SMB Accu Stop Pump Stop Soft Stop Parameter 33 Stop Time This sets the time period ...

Страница 13: ...ew or Review the Metering Information Access the metering parameters by selecting PARAMETER MONITORING and then METERING Press enter to view any selected value Step Action 1 Press Esc to acknowledge the fault The fault information will be removed so that you can use the HIM 2 To View or Review the fault information Go to MAIN MENU DIAGNOSTICS FAULTS VIEW FAULT QUEUE Or look at parameters 124 128 3...

Страница 14: ...value Extend the delay time to match the application requirements Undervoltage 21 running Supply voltage is less than user programmed value The delay time is too short for the application Check power system and correct if necessary Correct the user programmed value Extend the delay time to match the application requirements Overload 22 running Motor overloaded Overload parameters are not matched t...

Страница 15: ...150 FPP25B 150 FPP25C N A 43 A B 150 FPP43B 150 FPP43C N A 60 A B 150 FPP60B 150 FPP60C N A 85 A B 150 FPP85B 150 FPP85C N A 108 A A 41391 800 01 41391 800 02 N A 135 A A 41391 800 03 41391 800 04 N A 108 A B 150 FPP108B 150 FPP108C 150 FPP108Z 135 A B 150 FPP135B 150 FPP135C 150 FPP135Z 201 A B 150 FPP201B 150 FPP201C 150 FPP201Z 251 A B 150 FPP251B 150 FPP251C 150 FPP251Z 317 A B 150 FPP317B 150...

Страница 16: ...Publication 150 QS001G EN P August 2008 40055 217 01 7 Superecedes Publication 150 QS001F EN P November 2006 Copyright 2008 Rockwell Automation Inc All Rights Reserved Printed in USA ...

Отзывы: