3-96
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
808
Anlg In2 Scale
Scales the range of Analog Input 2 to the range of
[Anlg In2 Data]. Enter the units you
want per volt or mA. For example: If Par 807 [Anlg In2 Value] = 0 - 10V and you enter “6” in
this parameter, Par 806 [Anlg In2 Data] will equal 0 - 60V.
Par 807 * Par 808 = Par 806.
Units:
Default:
Min/Max:
/V or /mA
0.1000
-/+2200000000.0000
✓
RW Real
809
Anlg In2 Offset
Applies an offset to Analog Input 2. Use the offset to correct for zero signal errors or to create
an offset to the actual input. The output of the A/D converter is summed with this parameter to
produce
[Anlg In2 Value].
Units:
Default:
Min/Max:
V/mA
0.0000
-/+20.0000
✓
RW Real
810
AI 2 Filt Gain
Provides the Lead term for the Analog Input 2 filter.
Default:
Min/Max:
1.0000
-/+5.0000
✓
RW Real
811
Anlg In2 Filt BW
Sets the frequency for the Analog Input 2 filter.
Units:
Default:
Min/Max:
R/S
0.0000
0.0000/3760.0000
✓
RW Real
812
Anlg In3 Data
Displays the scaled final value for Analog Input 3.
Default:
Min/Max:
0.0000
-/+2200000000.0000
RO Real
813
Anlg In3 Value
Displays the actual input value at Analog Input 3. Analog Input 3 is a uni-polar voltage input
only and cannot be configured for current.
Type of Input
= Voltage
Polarity
= Uni-Polar
Resolution
= 10 bit (0 to +1023)
Note: When bit 2 “AI3 Thermstr” of
[Analog I/O Units] is set (= 1), this parameter
cannot be viewed from the HIM.
Units:
Default:
Min/Max:
Volts
0.0000
0.0/10.0
RO Real
814
Anlg In3 Scale
Scales the raw analog input data plus the input offset (if any) to the desired data range. The
scaled data for Analog Input 3 is displayed in
[Anlg In3 Data] and is available for
usage in the drive. Enter the units you want per volt. For example: If Par 813 [Anlg In3 Value]
= 0 - 10V and you enter “6” in this parameter, Par 812 [Anlg In3 Data] will equal 0 - 60V.
Par 813 * Par 814 = Par 812.
Note: When bit 2 “AI3 Thermstr” of
[Analog I/O Units] is set (= 1), this parameter
cannot be viewed from the HIM.
Units:
Default:
Min/Max:
/Volts
0.1000
-/+2200000000.0000
✓
RW Real
815
Anlg In3 Offset
Applies an offset to Analog Input 3. Use the offset to correct for zero signal errors or to create
an offset to the actual input. The output of the A/D converter is summed with this parameter to
produce
[Anlg In3 Value].
Note: When bit 2 “AI3 Thermstr” of
[Analog I/O Units] is set (= 1), this parameter
cannot be viewed from the HIM.
Units:
Default:
Min/Max:
Volts
0.0000
-/+20.0
✓
RW Real
816
AI 3 Filt Gain
Provides the Lead term for the Analog Input 3 filter.
Note: When bit 2 “AI3 Thermstr” of
[Analog I/O Units] is set (= 1), this parameter
cannot be viewed from the HIM.
Default:
Min/Max:
1.0000
-/+5.0
✓
RW Real
817
Anlg In3 Filt BW
Provides the Lag term for the Analog Input 3 filter.
Note: When bit 2 “AI3 Thermstr” of
[Analog I/O Units] is set (= 1), this parameter
cannot be viewed from the HIM.
Units:
Default:
Min/Max:
R/S
0.0000
0.0000/3760.0000
✓
RW Real
No.
Name
Description
Values
Linkab
le
R
ead-Wr
ite
Da
ta
T
ype
Light
Heavy
[Al 2 Filt Gain
0.25
0.1
Par 811 [Anlg In2 Filt BW]
50
10
Light
Heavy
[Al 3 Filt Gain
0.25
0.1
Par 817 [Anlg In3 Filt BW]
50
10
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......