3-72
Programming and Parameters
PowerFlex 700S Phase II AC Drive User Manual -
Publication 20D-UM006G-EN-P – July 2008
No.
Name
Description
Values
Linka
b
le
Read-Write
Data T
ype
503
Current Reg BW
Sets the bandwidth for the current regulator.
[PWM Frequency] limits the maximum
value. Reducing the value reduces current regulator over-shoot.
Units:
Default:
Min/Max:
R/S
600
100/30000
RW 16-bit
Integer
504
PM AbsEncd Offst
Determined by auto-tune procedure.
Default:
Min/Max:
0
0/65535
RW 16-bit
Integer
505
PM TestWait Time
Defines the time interval used for the automated measurement of
[PM AbsEncd
Offst] for a Permanent Magnet (PM) motor.
Units:
Default:
Min/Max:
mSec
2000
500/5000
RW 16-bit
Integer
506
PM Test Idc Ramp
Defines the ramp rate of the Flux Producing (d-axis) current reference that is used for the
automated measurement of
[PM AbsEncd Offst] for a Permanent Magnet (PM)
motor.
Units:
Default:
Min/Max:
Scale:
%/mS
0.1
0.0/195.3
x 10
RW 16-bit
Integer
507
PM Test FreqRamp
Defines the ramp rate of the frequency reference that is used for the automated
measurement of
[PM AbsEncd Offst] for a Permanent Magnet (PM) motor.
Units:
Default:
Min/Max:
Scale:
%/mS
0.1
0.0/195.3
x 10
RW 16-bit
Integer
508
PM Test Freq Ref
Defines the frequency reference that is used for the automated measurement of
[PM AbsEncd Offst] for a Permanent Magnet (PM) motor.
Units:
Default:
Min/Max:
Scale:
%
10.0
-/+799.9
x 10
RW 16-bit
Integer
509
PM Test I Ref
Defines the amplitude of the Flux Producing (d-axis) current reference that is used for the
automated measurement of
[PM AbsEncd Offst] for a Permanent Magnet (PM)
motor.
Units:
Default:
Min/Max:
Scale:
%
30.0
0.0/799.9
x 10
RW 16-bit
Integer
510
FVC Mode Config
Configures Field Oriented Control (FOC) operation.
•
Bit 4 “SlipTuneDone” when set, the value in
[Rated Slip Freq] is used as the slip gain before the slip regulator becomes active, after power is cycled, or
when the drive is reset by the system. When the Slip Tune is completed, this bit will be automatically be set and Par 486 will be updated.
•
Bit 7 “Ids Comp En” setting this bit runs the Ids test, to establish the initial flux current level for the motor, and the inertia test (even if already run).
•
Bit 12 “SlipRsCompEn” when set, the stator resistance will be compensated based on the output of the slip regulator.
•
Bit16 “ManuCurOffst” when set,
[Iu Offset] is used as the phase U current feedback offset value and
[Iw Offset] is used as the phase W current
feedback offset value. When this bit is not set (default) the phase U and W current feedback offset values are automatically updated when the drive is in a stop
condition except during the first 10 seconds of the stop condition.
•
Bit17 “ManuVltOffst” when this bit is set,
[Vuv Fdbk Offset] is used as the UV voltage feedback offset value and
[Vvw Fdbk Offset] is used as
the VW voltage feedback offset value.
•
Bit 23 “SyncTrans En” when set (default), the synchronous transfer algorithm using voltage feedback data is active.
Notes: Bit changes were made for firmware version 2.03. Bits 10 and 11 were added for firmware version 3.01. Changed bit 3 from “Reserved” to “FastFluxDsbl” for
firmware version 3.03. Added bits 4, 7, 12, 16, 17 and 23 for firmware version 4.001.
!
ATTENTION: Do not modify this parameter.
Motor/Drive instabilities and damage could result.
Options
Reser
ved
Reser
ved
Reser
ved
Reser
ved
Reser
ved
Reser
ved
Reser
ved
Reser
ved
Sync
Tr
an
s En
SrLs
s RdTh
ru
Vlt
M
inor
LpEn
SoftAdp
tGain
Reser
ved
Reser
ved
Man
uVltOffst
Ma
nu
Cu
rOff
st
LwSpdR
flct
Wv
Slip Reg
En
SlipGa
in
Es
t
SlipRs
CompEn
SlipPr
loa
dEn
SlipSle
w
RtEn
ReflW
av
eComp
BusGain Comp
Ids
Co
mp
En
Flux Reg Use
Flux Reg En
SlipT
uneDo
ne
F
ast
Fl
ux
D
sb
l
Reser
ved
Reser
ved
Reser
ved
Default
0
0
0
0
0
0
0
0
1
0
1
0
0
0
0
0
0
1
1
0
0
0
1
1
0
1
1
0
0
0
0
0
Bit
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
0 = False
1 = True
Содержание PowerFlex 700S
Страница 1: ...USER MANUAL Firmware Versions 1 xxx 4 002 PowerFlex 700S High Performance AC Drive Phase II Control ...
Страница 58: ...2 8 Start Up PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 147: ...Programming and Parameters 3 89 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 278: ...D 8 HIM Overview PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 Notes ...
Страница 316: ...Index 6 PowerFlex 700S Phase II AC Drive User Manual Publication 20D UM006G EN P July 2008 ...
Страница 317: ......