Rockwell Automation Publication SYSLIB-RM057A-EN-P - January 2017
55
PowerFlex 6000 Drive (P_PF6000)
Engineering Tab Page 4
The following table shows the functions on the Engineering tab page 4.
Table 18 - Engineering Tab Page 4 Description
Function
Action
Security
Configuration Parameters
Operator ‘Stop’
command available
in any mode
Check (= 1) so that the OCmd_Stop
has priority and is accepted at any
time.
Clear this checkbox (= 0) so that the
OCmd_Stop works only in Operator
or Maintenance mode.
Engineering
Maintenance
(Code E)
Cfg_OperStopPrio
Allow local ‘Start’ or
‘Stop’ without
triggering alarm
Check (= 1) to allow local start/stop
without an alarm.
Clear this checkbox (= 0) to
start/stop from the HMI or program
only.
Cfg_AllowLocal
Time to ramp speed
feedback in
Loopback Test (sec)
Enter the time, in seconds, to ramp
speed feedback when in Simulation.
Cfg_SimRampT