Using RTU Master Mode
D-5
4.
Remove power from the drive to which the wireless connection has
been made. Then electrically connect all drives to create the RTU
Master network. Refer to
System Wiring on page D-6
for network
wiring details.
Using DriveExplorer
1.
On the DriveExplorer WIM Linear List screen (
Figure D.5
),
double-click WIM
Parameter 01 - [Adapter Cfg]
and set its value
to “3 = RTU Master.”
Figure D.5 DriveExplorer WIM Linear List Screen
2.
Remove power from the drive to which the wireless connection has
been made. Then electrically connect all drives to create the RTU
Master network. Refer to
System Wiring on page D-6
for network
wiring details.
Using DriveExecutive
1.
In the Value column of the DriveExecutive WIM Linear List screen
(
Figure D.6
), click on the WIM
Parameter 01 - [Adapter Cfg]
pull-down list and set its value to “3 = RTU Master.”