Rockwell Automation MSR127RTP Скачать руководство пользователя страница 2

Safety Ratings

Standards

EN 954-1, ISO 13849-1, IEC/EN 60204-1, IEC 60947-4-1, IEC 60947-5-1, ANSI B11.19, AS4024.1

Safety Classification

Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1

Functional Safety Data 

 

Note

: For up-to-date information, visit

http://www.ab.com/safety/

PFH

D

: < 1.45 x 10

-9

MTTFd: > 398 years
Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the
architecture and application characteristics

Certifications

CE Marked for all applicable directives, cULus and BG

Power Supply

Input Power Entry

24V AC/DC, 115V AC or 230V AC 50/60 Hz

Power Consumption

2 W

Inputs

Safety Inputs

1 N.C. or 2 N.C. or LC

Input Simultaneity

Infinite (ch2 before ch1) with Auto Reset

Input Resistance, Max.

110 

W

Reset

Auto./Manual or Monitored Manual

Power On Delay/
Recovery Time

1 second

/

100 ms

Response Time

15 ms

Outputs

Safety Contacts

3 N.O.

Auxiliary Contacts

1 N.C.

Thermal Current

I

lth

Units with 24V AC/DC supply: 3 x 4 A or 2 x 5 A nonswitching
Units with 115/230V AC supplies: 3 x 3 A or 2 x 4 A or 1 x 5 A nonswitching

Rated Impulse withstand Voltage

2500V

Switching Current @ Voltage, Min.

10 mA/10V

Fuses, Output

External 6 A slow blow or 10 A fast acting

Electrical Life (Operations)

(With surge suppression)
250V AC/6 A/1500VA cos

f

 = 1…0.1 M

250V AC/2.5 A/625VA cos

f

 = 1…0.5 M

250V AC/1.5 A/375VA cos

f

 = 0.35…0.3 M

250V AC/5 A/1250VA cos

f

 = 0.6…0.1 M

24V DC/2 A/48 W = 1 M
10V DC/0.01 A/0.1 W = 2 M

Mechanical Life

2,000,000 operations

Utilization Category

UL: B300, R300 5 A/250V AC, 24V DC

Resistive: AC-1

5 A/250V AC

 

Resistive: DC-1

5 A/24V DC

 

Inductive: AC-15

5 A/250V AC

 

Inductive: DC-13

3 A/24V DC

5 A/24V DC @ 6 ops/min

Environmental and Physical Characteristics

Enclosure Type Rating/
Terminal Protection

IP40 (NEMA 1)

/

IP20

Operating Temperature [C (F)]

‐5…+55 ° (23…131 °)

Vibration

10…55 Hz, 0.35 mm

Shock

10 g, 16 ms 100 shocks

Mounting

35 mm DIN Rail

Weight [g (lb)]

24V DC: 210 (0.46), 115/230V AC: 260 (0.57)

Conductor Size, Max.

0.2…4 mm

2

 (24…12 AWG)

 

 Usable for ISO 13849‐1:2006 and IEC 62061. Data is based on the following assumptions:

- Mission time/Proof test interval of 20 years
- Functional test at least once within six-month period

Product Selection

Отзывы: