![Rockwell Automation External Dynamic Brake Kit Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/rockwell-automation/external-dynamic-brake-kit/external-dynamic-brake-kit_installation-instructions_1475440002.webp)
www.rockwellautomation.com
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Power, Control and Information Solutions Headquarters
Publication RA-IN004B-EN-P – April 2011
Supersedes RA-IN004A-EN-P – January 2003
Copyright © 2011 Rockwell Automation, Inc. All rights reserved.
Thermostat Contact Rating:
125 VAC, 15 A, Opens at 227 °C (440 °F) Closes at 1
8
2 °C (359 °F)
Application Cross-Reference
Note 1:
Always check resistor ohms against minimum resistance for drive being used.
Note 2:
Duty cycle listed is based on full speed to zero speed deceleration.
For constant regen at full speed, duty cycle capability is half of what is listed.
Application Type 1 represents maximum capability up to 100% braking torque where possible.
Application Type 2 represents more than 100% braking torque where possible, up to a maximum of 150%.
Drive and Motor
Size
kW (HP)
Part Number
Resistance
Ohms ±5%
Continuous Power
kW
Max Energy
kJ
Max Braking
Torque
% of Motor
Application Type 1
Application Type 2
Braking Torque
% of Motor
Duty Cycle
%
Braking Torque
% of Motor
Duty Cycle
%
100…120 Volt AC Input Drives
0.75 (1)
AK-R2-091P500
91
0.0
8
6
17
21
8
%
100%
23%
150%
31%
1.1 (1.5)
AK-R2-091P500
91
0.0
8
6
17
164%
100%
16%
14
8
%
11%
200…240 Volt AC Input Drives
0.37 (0.5)
AK-R2-091P500
91
0.0
8
6
17
293%
100%
46%
150%
31%
0.75 (1)
AK-R2-091P500
91
0.0
8
6
17
21
8
%
100%
23%
150%
15%
1.5 (2)
AK-R2-091P500
91
0.0
8
6
17
109%
100%
11%
109%
11%
2.2 (3)
AK-R2-047P500
47
0.166
33
144%
100%
15%
144%
11%
4 (5)
AK-R2-047P500
47
0.166
33
79%
79%
11%
N/A
N/A
5.5 (7.5)
AK-R2-030P1K2
30
0.26
52
90%
90%
10%
N/A
N/A
7.5 (10)
AK-R2-030P1K2
30
0.26
52
66%
66%
10%
N/A
N/A
11 (15)
See Note 3
15
0.52
104
90%
90%
10%
N/A
N/A
15 (20)
See Note 3
15
0.52
104
66%
66%
10%
N/A
N/A
400…480 Volt AC Input Drives
0.37 (0.5)
AK-R2-360P500
360
0.0
8
6
17
305%
100%
47%
150%
31%
0.75 (1)
AK-R2-360P500
360
0.0
8
6
17
220%
100%
23%
150%
15%
1.5 (2)
AK-R2-360P500
360
0.0
8
6
17
110%
100%
12%
110%
11%
2.2 (3)
AK-R2-120P1K2
120
0.26
52
197%
100%
24%
150%
16%
4 (5)
AK-R2-120P1K2
120
0.26
52
124%
100%
13%
124%
10%
5.5 (7.5)
AK-R2-120P1K2
120
0.26
52
90%
90%
10%
N/A
N/A
7.5 (10)
AK-R2-120P1K2
120
0.26
52
66%
66%
10%
N/A
N/A
11 (15)
See Note 3
60
0.52
104
90%
90%
10%
N/A
N/A
15 (20)
See Note 3
60
0.52
104
66%
66%
10%
N/A
N/A
600 Volt AC Input Drives
0.37 (0.5)
AK-R2-360P500
360
0.0
8
6
17
274%
100%
46%
150%
31%
0.75 (1)
AK-R2-360P500
360
0.0
8
6
17
251%
100%
23%
150%
15%
1.5 (2)
AK-R2-360P500
360
0.0
8
6
17
172%
100%
11%
150%
8
%
2.2 (3)
AK-R2-120P1K2
120
0.26
52
193%
100%
24%
150%
16%
4 (5)
AK-R2-120P1K2
120
0.26
52
1
8
5%
100%
13%
150%
9%
5.5 (7.5)
AK-R2-120P1K2
120
0.26
52
141%
100%
9%
141%
7%
7.5 (10)
AK-R2-120P1K2
120
0.26
52
103%
100%
7%
103%
7%
11 (15)
See Note 3
60
0.52
104
141%
100%
9%
141%
7%
15 (20)
See Note 3
60
0.52
104
103%
100%
7%
103%
7%
AC Drive
4
BR1
BR+
BR2
BR-
!
ATTENTION:
AC drives do not offer protection for externally mounted brake resistors,
especially in the case of brake IGBT failure. A risk of fire exists if external braking
resistors are not protected. External resistor packages must be protected from over
temperature or the protective circuit shown, or equivalent, must be supplied.
AC Drive
5
Thermostat
Connectors
Power On
R (L1)
S (L2)
T (L3)
Power Source
DB Resistor Thermostat
Power Off
M
M
(Input Contactor) M
Three-Phase
AC Input
!
ATTENTION:
Resistor temperature may exceed 200
degrees C.
Note 3:
For 11 and 15 kW (15 and 20 HP) normal duty external resistor applications, use two
7.5 kW (10 HP) size resistors wired in parallel.