44
Rockwell Automation Publication KNX-TD005A-EN-P - October 2021
Kinetix 300 and Kinetix 350 EtherNet/IP Servo Drives
Circuit Breaker/Fuse Specifications
Kinetix 300 and Kinetix 350 servo drives use internal solid-state motor short-circuit protection and, when protected by suitable branch circuit
protection, are rated for use on a circuit capable of delivering up to 100,000 A (fuses) and 65,000 A (circuit breakers). These fuses and Allen-
Bradley circuit breakers are recommended for use with 2097-V
xx
PR
x-xx
drives.
Input Power UL Circuit-protection Specifications
Kinetix 300 and Kinetix 350 Drives
UL Applications
Drive Cat. No.
Drive Voltage
Phase
Fuses (Bussmann)
Cat. No.
Miniature CB
(1)
Cat. No.
(1) Bulletin 1492 and 1489 circuit protection devices have lower short-circuit current ratings than Bulletin 140M/MT devices.
See the
webpage for product literature with specific short-circuit ratings.
Motor Protection CB,
(2)
(3)
(4)
Self-protected CMC
Cat. No.
(2) For UL applications, Bulletin 140M/MT devices are applied as self-protected combination motor controllers.
(3) These Bulletin 140M/MT Motor Protection Circuit Breakers, when used as self-protected (Type E) devices, and Bulletin 1489 circuit breakers can be used on only WYE power systems (480Y/277V).
(4) The AIC ratings of the Bulletin 140M/MT devices can vary. See publication
or
.
2097-V31PR0-
xx
120V
Single-phase
(voltage doubler)
KTK-R-20 (20A)
1489-M1C200
140M-D8E-C20
140MT-D9E-C20
120/240V
Single-phase
KTK-R-10 (10A)
1489-M1C100
140M-C2E-C10
140MT-C3E-C10
2097-V31PR2-
xx
120V
Single-phase
(voltage doubler)
KTK-R-30 (30A)
1489-M1C300
140M-F8E-C32
120/240V
Single-phase
KTK-R-20 (20A)
1489-M1C200
140M-D8E-C20
140MT-D9E-C20
2097-V32PR0-
xx
240V
Single-phase
KTK-R-20 (20A)
1489-M1C150
140M-D8E-C16
140MT-D9E-C16
2097-V32PR2-
xx
KTK-R-20 (20A)
1489-M1C200
140M-D8E-C20
140MT-D9E-C20
2097-V32PR4-
xx
KTK-R-30 (30A)
1489-M1C300
140M-F8E-C32
2097-V33PR1-
xx
120/240V
Single-phase
KTK-R-20 (20A)
1489-M1C200
140M-D8E-C20
140MT-D9E-C20
240V
Three-phase
KTK-R-15 (15A)
1489-M3C150
140M-D8E-C16
140MT-D9E-C16
2097-V33PR3-
xx
120/240V
Single-phase
KTK-R-20 (20A)
1489-M1C200
140M-D8E-C20
140MT-D9E-C20
240V
Three-phase
KTK-R-15 (15A)
1489-M3C150
140M-D8E-C16
140MT-D9E-C16
2097-V33PR5-
xx
120/240V
Single-phase
KTK-R-30 (30A)
1489-M1C300
140M-F8E-C32
240V
Three-phase
KTK-R-20 (20A)
1489-M3C200
140M-D8E-C20
140MT-D9E-C20
2097-V33PR6-
xx
120/240V
Single-phase
LPJ-40SP (40A) Class J
N/A
140M-F8E-C32
240V
Three-phase
KTK-R-30 (30A)
1489-M3C300
2097-V34PR3-
xx
480V
Three-phase
KTK-R-10 (10A)
1489-M3C100
140M-C2E-C10
140MT-C3E-C10
2097-V34PR5-
xx
KTK-R-10 (10A)
1489-M3C100
140M-C2E-C10
140MT-C3E-C10
2097-V34PR6-
xx
KTK-R-20 (20A)
1489-M3C200
140M-D8E-C20
140MT-D9E-C20