Rockwell Automation Publication 6200-UM001C-EN-P - July 2018
19
Install the Thin Client or Computer
Chapter 3
To comply with EN 55024 and EN 55032, use the following for cable types.
Installation Guidelines
Follow these guidelines to make sure your VersaView thin client or industrial
computer provides service with excellent reliability:
• The installation site must have sufficient power.
• In dry environments, static charges can build up easily. Proper grounding
of the thin client or computer helps to reduce static discharges, which
can cause shock and damage electronic components.
• The ambient air temperature must not exceed the maximum operating
temperature in
.
Table 3 - Maximum Operating Temperature Ranges
Cable Type
Required Attribute
Cable Type
Required Attribute
LAN
Shielded
Line-out
Unshielded
USB
Line-in
Serial RS-232
Microphone
DVI
DC power
DisplayPort
AC power
Unshielded
(1)
(1) For the applicable power adapters, see the Power Connection table rows in
Connect Peripherals on page 28
.
Mini-DisplayPort
HDMI
VGA
ATTENTION:
For applications with an AC power source, the shipped
or optional AC-to-DC power adapter must be plugged into a
grounded outlet to maintain an electrically safe installation.
VersaView Model
Cat. Nos.
Temperature, max
5200
ThinManager thin client
Non-display
6200T-BA
0…50 °C (32…122 °F)
6200T-KB
0…55 °C (32…131 °F)
6200T-RC, 6200T-RE
0…45 °C (32…113 °F
6200T-NA
-20…+60 °C (-4…+140 °F)
Display
6200T-xxWA
0…50 °C (32…122 °F)
5400 Industrial Computers
Non-display
6200P-NSxA1
-20…+60 °C (-4…+140 °F)
Display
6200P-xxWS3x1
0…50 °C (32…122 °F)
IMPORTANT
VersaView thin clients and industrial computers can operate at a
range of extremes. However, the life span of any electronic device is
shortened if you continuously operate it at its highest rated
temperature, which includes the touch screen and LCD panel.
Содержание Allen-Bradley VersaView 5000 ThinManager Series
Страница 6: ...6 Rockwell Automation Publication 6200 UM001C EN P July 2018 Table of Contents Notes ...
Страница 44: ...44 Rockwell Automation Publication 6200 UM001C EN P July 2018 Chapter 5 Configure the UEFI BIOS Settings Notes ...
Страница 48: ...48 Rockwell Automation Publication 6200 UM001C EN P July 2018 Chapter 6 Troubleshoot the System Notes ...
Страница 68: ...68 Rockwell Automation Publication 6200 UM001C EN P July 2018 Appendix A Install Accessories Notes ...
Страница 70: ...70 Rockwell Automation Publication 6200 UM001C EN P July 2018 Index Notes ...
Страница 71: ......