56
Rockwell Automation Publication 6000-IN100B-EN-P - October 2020
Appendix A Pre-Commissioning
Print the following information:
Name:
Date:
Company:
Phone:
Pages:
Fax:
Drive Serial Number:
Rockwell Automation Service Engineer Requested (YES/
NO):
Scheduled Commissioning Date:
Table 6 - Receiving and Unpacking
Initials
Date
Check
The drives have been checked for shipping damage upon receiving.
After unpacking, the items received are verified against the bill of materials.
Any claims for breakage or damage, whether concealed or obvious, are made
to the carrier by the customer as soon as possible after receipt of shipment.
All packing material, wedges, or braces are removed from the drive.
Table 7 - Installation and Mounting
Initials
Date
Check
The drive is securely fastened in an upright position, on a level surface.
The Isolation Transformer Cabinet, Power Module Cabinet, and Bypass Cabinet
(if applicable) are correctly installed.
Lifting Angles have been removed.
Bolts are inserted into original location on top of drive (help prevent leakage of
cooling air).
All contactors and relays have been operated manually to verify free
movement.
The back plates to the cabinets have been reinstalled.
Table 8 - Safety
Initials
Date
Check
The grounding of the drive should be in accordance with national and local
electrical codes.
Table 9 - Control Wiring
Initials
Date
Check
All low voltage wiring entering the drive is labeled, appropriate wiring diagrams
are available, and all customer interconnections are complete.
All AC and DC circuits are run in separate conduits.
All wire sizes that are used are selected by observing all applicable safety and
national and local electrical codes.
Remote I/O is correctly installed and configured (if applicable).
All 3-phase control wiring is within specified levels and has been verified for
proper rotation, UVW.
All single-phase control wiring is within specified levels and has grounded
neutrals.
Control lines must be shielded and grounded. Control and Power lines must run
in separate conduits.
The electrical safety interlock wiring to input circuit breaker is correctly
installed.
Содержание Allen-Bradley PowerFlex 6000T
Страница 1: ...PowerFlex 6000T Drives Catalog Number 6000T Installation Instructions Original Instructions ...
Страница 58: ...58 Rockwell Automation Publication 6000 IN100B EN P October 2020 Appendix A Pre Commissioning Notes ...
Страница 60: ...60 Rockwell Automation Publication 6000 IN100B EN P October 2020 Appendix B Torque Requirements Notes ...
Страница 62: ...62 Rockwell Automation Publication 6000 IN100B EN P October 2020 Appendix C General Wire Categories Notes ...
Страница 74: ...74 Rockwell Automation Publication 6000 IN100B EN P October 2020 Index Notes ...