![Rockwell Automation Allen-Bradley PowerFlex 400P Series Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-powerflex-400p-series/allen-bradley-powerflex-400p-series_quick-start-manual_1475487027.webp)
PowerFlex 400P Adjustable Frequency AC Drive Quick Start
English-25
R241
R244
R247
[Aux 1 Start Freq]
[Aux 2 Start Freq]
[Aux 3 Start Freq]
0.0/320.0 Hz
0.1 Hz
50.0 Hz
R242
R245
R248
[Aux 1 Stop Freq]
[Aux 2 Stop Freq]
[Aux 3 Stop Freq]
0.0/320.0 Hz
0.1 Hz
25.0 Hz
R243
R246
R249
[Aux 1 Ref Add]
[Aux 2 Ref Add]
[Aux 3 Ref Add]
0.0/100.0%
0.1%
0.0%
R250 [Aux Start Delay]
0.0/999.9 Secs
0.1 Secs
5.0 Secs
R251 [Aux Stop Delay]
0.0/999.9 Secs
0.1 Secs
3.0 Secs
R252 [Aux Prog Delay]
0.00/60.00 Secs
0.01 Secs
0.50 Secs
R253 [Aux AutoSwap Tme] 0.0/999.9 Hrs
0.1 Hrs
0.0 Hr
R254 [Aux AutoSwap Lvl]
0.0/100.0%
0.1%
50.0%
No.
Parameter
Min/Max
Display/Options
Default
Advanced Display Group Parameters
No.
Parameter
Min/Max
Display/Options
Default
d301 [Control Source]
0/99
Digit 0: Start Command
0 = Keypad
1 = Terminal Block
2 = Communications
Digit 1: Speed Command
0 = Local Keypad Pot
1 = A142
2 = Analog Input 1
3 = Analog Input 2
4 = A143-146
5 = Communications
Read Only
d302 [Contrl In Status]
0/1
(1 = Condition True)
Read Only
d303 [Comm Status]
0/1
(1 = Condition True)
Digit 0: Received Good Message Packet
Digit 1: Transmitting Message
Digit 2: DSI Peripheral Connected
Digit 3: Received Bad Message Packet
Read Only
d304 [PID Setpnt Displ]
0.0/100.0%
0.1%
0.0%
d305
d306
[Analog In 1]
[Analog In 2]
0.0/120.0%
0.1%
0.0%
d307
d308
d309
[Fault 1 Code]
[Fault 2 Code]
[Fault 3 Code]
0/122
1
Read Only
d310
d312
d314
[Fault 1 Time-hr]
[Fault 2 Time-hr]
[Fault 3 Time-hr]
0/32767 Hrs
1 Hrs
Read Only
d311
d313
d315
[Fault 1 Time-min]
[Fault 2 Time-min]
[Fault 3 Time-min]
0.0/60.0 Min
0.1 Min
Read Only
d316 [Elapsed Time-hr]
0/32767
1 Hr
Read Only
d317 [Elapsed Time-min]
0.0/60.0 Min
0.1 Min
Read Only
d318 [Output Powr Fctr]
0.0/180.0 deg
0.1 deg
Read Only
d319 [Testpoint Data]
0/FFFF
1 Hex
Read Only
d320 [Control SW Ver]
1.00/99.99
0.01
Read Only
d321 [Drive Type]
Used by Rockwell Automation field service personnel.
d322 [Output Speed]
0.0/100.0%
0.1%
Read Only
d323 [Output RPM]
0/24000 RPM
1 RPM
Read Only
d324 [Fault Frequency]
0.00/320.00 Hz
0.01 Hz
Read Only
Display Digit (Right to Left)
I/O Terminal
Control Input
0
02
Start/FWD In
1
03
Dir/REV In
2
01
Stop Input
3
05
Digital In 1
4
06
Digital In 2
5
07
Digital In 3
6
08
Digital In 4
22P-QS001C-EN-P.fm Page 25 Thursday, March 30, 2017 5:55 PM