48
Rockwell Automation Publication 20P-TD001K-EN-P - January 2021
PowerFlex DC Drive and Field Controller Technical Data
PowerFlex DC Drives and Field Controller Circuit Protection
The tables on the following pages provide the fuses that are required to help protect the armature and field circuits. Externally mounted
fuses (as indicated in Frame A and B Fuse Designations) must be sourced separately when installing the drive. Internally mounted fuses are
provided with the drive. See page
for frames C and D fuse information.
PowerFlex DC Drives Frame A and B Fuse Information
PowerFlex DC Drives Frames A and B AC Input Line Fuses
AC input line fuses are externally mounted for frame A and B drives and must be sourced separately. See Fuse Code FS1 in PowerFlex DC
Drives Frame A and B Fuse Information on page
.
230V AC Input Drives
Fr
am
e
Drive Current
Rating Code
DC Amps
AC Line
Amps
Bussmann
Mersen
Ferrule FWP Type
North American FWP Type
Ferrule A70QS Type
North American A70P /
A70QS Type
A
7P0
7
5.7
FWP-10A14F
FWP-10B
A70QS10-14F
A70P10-4
9P0
9
7.4
FWP-15A14F
FWP-15B
A70QS16-14F
A70P15-4
012
12
9.8
FWP-20A14F
FWP-20B
A70QS20-14F
A70P20-4
020
20
16
FWP-25A14F
FWP-25B
A70QS25-14F
A70P25-4
029
29
24
FWP-40A22F
FWP-40B
A70QS40-22F
A70QS40-4
038
38
31
FWP-63A22F
FWP-60B
A70QS63-22F
A70QS60-4
055
55
45
FWP-80A22F
FWP-80B
A70QS80-22F
A70QS80-4
073
73
60
—
FWP-100A
—
A70QS100-4K
093
93
76
FWP-150A
A70QS150-4K
110
110
90
FWP-175A
A70QS175-4K
B
146
146
119
—
FWP-250A
—
A70QS250-4
180
180
147
FWP-300A
A70QS300-4
218
218
178
FWP-350A
A70QS350-4
265
265
217
FWP-400A
A70QS400-4
360
360
294
FWP-600A
A70QS600-4K
434
434
355
FWP-600A
A70QS600-4
FS1
FS2
M
U V W
C D
FS3
C1 D1
U1 V1
FS1 = Externally
mounted fuses for
the armature
converter on the AC
input side.
FS2 = Externally
mounted fuses for
the armature circuit
on the DC side.
FS3 = Internally
mounted fuses for
the field circuit on
the AC input side.