Rockwell Automation Publication 750-IN115B-EN-P - March 2020
PowerFlex 755T Frames 5 and 6 EMC C2 Filter Kits
Frame 6 EMC C2 Filter Installation
Follow these steps to install the frame 6 EMC C2 filter kit.
1. Loosen the eight captive M4 slotted-torx screws on the front cover and remove the cover from the EMC C2 filter assembly.
2. Loosen the eight captive M4 slotted-torx screws on the bottom cover and remove the cover from the EMC C2 filter assembly.
3. To drill the required holes for an AC input power wire conduit fitting, use the pilot hole in the EMC C2 filter conduit box bottom plate.
1, 2
M4 (Captive)
T20
2.6 N
•
m (23 lb
•
in)
Pilot hole for AC input power and
ground wire conduit fitting.