Rockwell Automation Allen-Bradley Photoswitch 45DMS-B8LAT1-D4 Скачать руководство пользователя страница 5

Rockwell Automation Publication 45DMS-IN001A-EN-P - August 2018

5

PHOTOSWITCH Distance Measurement Sensor

To Change the Sensor Output Mode Setting

Press and release the button for less than 1 second within 10 seconds to 

toggle from L.O. to D.O., the selection indicated by the orange 

indicator. 
The sensor retains the setting per the last button depression and returns 

to the run mode 10 seconds after the last button is depressed.

Output Type Selection: Auto PNP/NPN, Dedicated NPN, 

Dedicated PNP

The default setting is Auto PNP/NPN. The sensor monitors the load 

connection and automatically configures for the proper operation, for 

example, PNP or NPN. If no load is connected, the sensor defaults to 

PNP.
The following applications are covered with dedicated PNP or 

dedicated NPN selection.

1. Parallel wiring of multiple sensor outputs: select dedicated PNP 

or dedicated NPN setting, as needed.

2.  Select dedicated NPN if the load is connected to another 

power supply than the power used for the sensor.

Selection can be made as follows.

1. To access output type: Press and hold the push button for 12 

seconds (until both indicators start flashing synchronously). At 

the release of the button, the slow flashing of the indicator (or 

indicators) shows the current setting of the output type as 

follows:
a. Auto PNP/NPN: Both indicators flashing (synchronously)
b. Dedicated NPN: Green indicator flashing
c. Dedicated PNP: Orange indicator flashing

2. To change output type: To select desired type, press and release 

the push button within 10 seconds. Each press of the button 

cycles to the next output setting. The indicators show the type 

that is selected. The sensor retains the setting per the last button 

depression and returns to the run mode 10 seconds after the last 

button is pressed.

Push Button Lock/Unlock

The push button or remote teach (RT) can be used to stop 

unauthorized users from changing teach settings.
Permanent lock: The push button is permanently locked by connecting 

the white wire (pin 2) to -V. To unlock the push button, disconnect the 

white wire (pin 2) on the catalog number 45DMS-B8LAT1-D4 sensor 

or the gray wire (pin 5) on the catalog number 45DMS-B8LGT1-D5 

sensor.

Remote Teach (RT)

The sensor can be taught remotely via the gray wire (pin 5). Connection 

to -V acts the same as the button being pressed and no connection is the 

same as the button not being pressed. The sensor can be taught by 

following the same teach/timing sequence as used in the push button 

teach. For example:

• Connect to the +V for more than three seconds to teach the 

“target,”

• Disconnect from the +V,
• Remove the target and connect to the -V for less than one 

second to teach the second condition. See 

Teach the Sensor on 

page 4

 for additional information.

All push button functions can be implemented via Remote Teach.

Factory Default Settings

To reset the sensor configuration to the factory default settings, the 

operator has to perform the following steps:

1. Remove power to the unit by unplugging the cordset
2. Press the Q or Q

A

 buttons

3. With the Q or Q

A

 buttons pressed, plug in the cordset that 

provides power to the sensor. Keep the button pressed for at 

least 10 seconds until both LEDs on the unit blink 

simultaneously 3 times.

Wiring Diagrams

The quick-disconnect connector is shown 

Figure 7

. The pin numbers 

correspond to the male connectors on the sensor.

 Figure 7 - Micro (M12) Male QD Pigtail/Male QD (5-pin)

 Figure 8 - Micro (M12) Male QD Pigtail/Male QD (4-pin)

 Figure 9 - Approximate Dimensions [mm (in.)]

-U

B

3 BU

Q

1

/IO-Link 4 BK

IN

5 GY

-

+U

B

Q

2

1
2

BN
WH

+

Auto-Detect

-U

B

3 BU

Q

1

/IO-Link 4 BK

IN

5 GY

-

+U

B

Q

2

1
2

BN
WH

+

Auto-Detect

1

B

INPUT

Q/IO-Link

-U B

4 BK

3 BU

+

-

+U

Auto-Detect

2 WH

1

BN

3

 

1

50.08 (1.97)

23 (0.90)

4.3 (0.17)

Teach-in

LED 1

LED 2

5.8 (0.23)

Receiver

Emitter

8.6

(0.34)

M12x1

28.4

(1.12)

44

(1.73)

46

(1.81)

50

(1.97)

13.95

(0.55)

16 (0.63)

Содержание Allen-Bradley Photoswitch 45DMS-B8LAT1-D4

Страница 1: ...t applications Eye Safe Class 1 Laser for ease of alignment and installation Distance measurement background suppression and background reflection sensing modes selectable using IO Link Discrete only...

Страница 2: ...w setting Figure 1 Standard Teach Operation The sensor can also operate as a background reflection sensor when configurated via IO Link See the 45DMS IO Link user manual for more information on how to...

Страница 3: ...ition has been taught 2 Teach far distance second condition Place the target at the desired far distance Press and release the button The teach process is complete TeachAnalogOutput QA 1 Teach near di...

Страница 4: ...separation of at least 60 mm 2 35 in 1 Teach the target first condition Place the target at the desired distance Press and hold the push button for three seconds until the orange and green indicator...

Страница 5: ...ton or remote teach RT can be used to stop unauthorized users from changing teach settings Permanent lock The push button is permanently locked by connecting the white wire pin 2 to V To unlock the pu...

Страница 6: ...mm Distance m horizontal x vertical y 5 4 3 2 1 0 Distance m Axial Object Approach 0 1 2 3 4 5 0 8 mm 1 6 mm 2 5 mm Repeatability 50 Hz 3 2 1 Gray 18 2 Black 6 3 White 90 1 15 mm 6 1 10 mm 5 mm 25 mm...

Страница 7: ...ensor protection Reverse polarity and short circuit Discrete Output Response time 2 ms for both Q and QA Output type Auto PNP or NPN on power up Load current 100 mA max Analog Output Range 4 20 mA def...

Страница 8: ...how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase A...

Отзывы: