Rockwell Automation Publication 440R-IN088A-EN-P - July 2022

3

Minotaur MSR138DP, MSR138.1DP Monitoring Safety Relay Installation Instructions

Installation

Do not install this product until the installer obtains a copy of the instructions of 
the manufacturer, in a language that they can understand. This instruction 
publication is available in multiple languages at 

rok.auto/literature

.

Figure 1 - Mounting

Mount the enclosure to a minimum of IP54.

Figure 2 - Removable Terminals (P versions only)

To remove the terminals, insert a screwdriver and slowly move as shown in 

Figure 2

.

Wiring Examples

Figure 3 - Example 1

Figure 3

 shows dual-channel E-stop, cross fault monitored, and monitored reset.

Circuit Diagram

Figure 4 - Diagram

Approximate Dimensions

Figure 5 - Dimensions [mm (in.)]

L1

N

E-stop

E-stop

Reset

Timer Override

Feedback Loop

Table 2 - Circuit Diagram Explanation

Abbreviation

Description

A1, A2

Power

S11, S12, S21, S22

Safety input (N.C.)

X1, X2, X3, X4, S33, S34

Link for auto reset

Y1, Y2

Monitoring loop feedback

Y39, Y40

Timer override

13, 14

Safety output 1 (N.O.)

23, 24

Safety output 2 (N.O.)

37, 38

Timer output 1 (N.O.)

47, 48

Timer output 2 (N.O.)

57, 58 

(1)

(1)

MSR 138DP

Timer output 3 (N.O.)

55, 56 

(2)

(2)

MSR 138.1DP

Timer output 3 (N.C.)

PWR

Status indicator illuminates green when the unit is powered, 
flashing green if cross-loop faults occur

CH1

Status indicator illuminates green when the safety output 
channel 1 activates

CH2

Status indicator illuminates green when the safety output 
channel 2 activates

CH1 IN

Status indicator illuminates green when the safety input channel 
1 closes

CH2 IN

Status indicator illuminates green when the safety input channel 
2 closes

CHT1

Status indicator illuminates green when Delayed Safety Output 
channel 1 activates

CHT2

Status indicator illuminates green when Delayed Safety Output 
channel 2 activates

Start

Status indicator illuminates green when the reset circuit closes

Overvoltage 

Protection

24V DC

AC

Start Logic

MSR 138DP

MSR 138.1DP

Logic 

Channel 1

Logic 

Channel 2

Timer 

Override

ST

AR

T

PWR

Содержание Allen-Bradley Minotaur MSR138DP

Страница 1: ...r manipulation can result in serious injuries Do not defeat tamper remove or bypass this unit ATTENTION If any malfunction or damage is present do not attempt to repair Replaced the unit before machine operation is allowed Do not dismantle the unit IMPORTANT The safety inputs of these products are described as normally closed N C that is with the guard closed the actuator in place where relevant a...

Страница 2: ...lose If the safety inputs and reset circuit concurrently close during power up the safety relay activates immediately R Manual monitored reset b In Manual Monitored Reset mode a signal change of the reset circuit S33 S34 is required and monitored A reset fault occurs if the safety inputs remain open while the reset circuit is closed Positive edge The safety relay is active once the safety inputs c...

Страница 3: ...21 S22 Safety input N C X1 X2 X3 X4 S33 S34 Link for auto reset Y1 Y2 Monitoring loop feedback Y39 Y40 Timer override 13 14 Safety output 1 N O 23 24 Safety output 2 N O 37 38 Timer output 1 N O 47 48 Timer output 2 N O 57 58 1 1 MSR 138DP Timer output 3 N O 55 56 2 2 MSR 138 1DP Timer output 3 N C PWR Status indicator illuminates green when the unit is powered flashing green if cross loop faults ...

Страница 4: ... MSR138 1DP safety relay in safety circuits according to DIN EN 60204 1 VDE 0113 part 1 Safety requirements that are specified in Specifications on page 1 are maximum based on the operation mode and wiring Specifications are applicable only if the safety function is demanded at least once within 6 months All diagnostic tests are conducted at least before next demand The mission time TM for the pro...

Отзывы: